HomeMy WebLinkAboutEDB Aquastore SA No. 5 for Tanglewood WTP GST No. 1. EXECUTIVE SUMMARY AGENDA ITEM: Supplemental Agreement No. 5 with Florida Aquastore & Utility Construction, Inc. (FAUC), for the Maintenance and Repair of Tanglewood Water Treatment Plant (WTP) Ground Storage Tank (GST)No.1 CCUA Project No. 1108-0062 Date: January 27, 2022 BACKGROUND: Clay County Utility Authority (CCUA) is required to inspect GSTs every five (5) years in accordance with Florida Department of Environmental Protection regulations. To complete the recommended maintenance resulting from the inspections, the Board of Supervisors approved a continuing contract with FAUC at the November 5, 2019, meeting. FAUC can repair CCUA's glass fused-to-steel GSTs. as a Staff coordinated with FAUC to provide the attached proposal for this repair work. The Water oo Treatment Department staff reviewed the proposal and agreed with the scope of work. 3 BUDGET: m Ce CCUA budgeted for this operating expense. The pricing FAUC provided in the attached quote is consistent with the continuing contract between CCUA and FAUC. RECOMMENDATION: Staff respectfully recommends the Board of Supervisors' approval of Supplemental Agreement No. 5 with FAUC in the amount of$46,323 for the Maintenance and Repair of Tanglewood WTP Ground Storage Tank No. 1. ATTACHMENTS: Supplemental Agreement No. 5 Florida Aquastore &Utility Construction, Inc., Proposal dated January 13, 2022 Florida Aquastore &Utility Construction, Inc., Tank Inspection Report dated January 7, 2022 //TLS (Author) //AB (Review) //TLS (Final) Supplemental Agreement No. 5 for the Maintenance and Repair of Tanglewood Water Treatment Plant Ground Storage Tank No. 1 Contractor: Florida Aquastore and Utility Construction, Inc. Owner: Clay County 4722 N.W. Boca Raton Blvd, Suite C-102 Utility Authority Boca Raton, Florida 33431 Date: February 1, 2022 Item Description of Services Florida Aquastore and Utility Construction, Inc., quote for $46,323 maintenance services dated January 13, 2022. Total Lump Sum Price Not to Exceed Without Prior Authorization $46,323 The Contract time shall commence on the needed date. This document along with the January 13, 2022, Proposal shall become an amendment to the existing Glass Fused-to-Steel Tank Rehabilitation Continuing Contract Bid No. 18/19-All and all provisions of the Agreement will apply hereto. All provisions, terms, and conditions of the existing Agreement will apply to this Supplemental Agreement. Accepted by: Date: Contractor: Thomas M. Whelchel President Florida Aquastore &Utility Construction, Inc. Accepted by: Date: Owner: Jeremy D. Johnston, PE, MBA Executive Director Clay County Utility Authority Florida Aquastore 4722 N.W. Boca Raton Blvd., Suite C-102, Boca Raton, Florida 33431 Phone: (561) 994-2400 Fax: (561) 994-2444 PROPOSAL AND CONTRACT TO: Clay County Utility DATE: January 13th, 2022 1082 Camp Francis Johnson ROJECT: CCUA Tanglewood Tank #1 Orange Park Fl 32065 Fusion Tank Attn. Mike Rapp Model 3924CFWT Cell: 904-755-3367 TERMS: 100% Upon Completion QITY We are pleased to quote you on the following work for UNIT EXTENSION acceptance within 30 days: PRICE 1 Mobilization and demobilization. Item U $5,000 $5,000 1 Remove and replace bottom wall panel for scaffold access. $3,560 $3,560 Item B 1 Materials and labor to pressure wash inside panels, bolts, $18,178 $18,178 and penetrations to clean metal. Re-seal all interior panel 'edges, Bolts and Penetrations with CIM 1061 for 24-foot sidewall. Item W 1 Material and labor to power wash, Scrape and power wire) $13,950 $13,950 brush all exterior sidewall panel edges to clean metal. Re- 'caulk all Panel edges with Manus-Bond sealer for 24-foot to sidewall. Item Y 2 Replace Roof Fans Item AA $2,400 $4,800 500 Replace Black polyethylene plastic exterior bolt caps as $1 $500 needed -Item X 1 Replace Manway Gasket $335 $335 TOTAL $46,323 4722 N.W. BOCA RATON BLVD. FLORIDA AQUASTORE SUITE C-102 TANK INSPECTION REPORT BOCA RATON, FL 33431 fQU _n.. TORE TEL: (561) 994-2400 water storage a wastewater treatment solutions Project Name: CCUA Tanglewood Tank #1 Tank Model: FUSION Owner: Clay County Utility Authority Address: 1476 Gifford Avenue Orange Park, FL 32065 Contact: Bryan Nall Cell #: 904-237-2015 Email: bnall@clayutility.org TANK MODEL: (1) 3129 FA Job No.: N/A. The tank is approximately 20 years old and is a Fusion (non Aquastore) model tank. Date of Report: January 7, 2022 to On January 6, 2022 an exterior and interior visual inspection of the Fusion water storage tank mentioned above was performed by Mr. Cedric Tomlin, a certified field superintendent for Florida Aquastore & Utility Construction, Inc. The purpose of the tank inspection was to establish the current condition of the tank, determine any deficiencies in the tank coating, tank appurtenances, and bolt seam sealer (the panel edge coating). The inspection was limited to visual observation and does not include examination of areas hidden from view which would require disassembly or material removal to expose. Florida Aquastore's inspection is limited in scope and does not include any evaluation of the structural integrity of the tank or its foundation. The recommendations contained in this report are solely based on the visual inspection and our experience with the manufacturer's maintenance requirements. The Owner can seek the services of a competent structural engineer to evaluate the structural integrity of the tank to assure that the tank can continue to be safely utilized. Page 1 of 26 4722 N.W. BOCA RATON BLVD. FtORI DR FLORIDA AQUASTORE SUITE C 102 _ TANK INSPECTION REPORT BOLA RATON, FL 33431 RQU n.. TOR TEL: (561) 994-2400 woter storage&wastewoter treatment solutions • tO Ihar 1111 _ _ . 440. • 11 — 04, • r. 2 Page 2 of 26 4722 N.W. BOCA RATON BLVD. FLORIDA AQUASTORE SUITE C 102 TANK INSPECTION REPORT BOLA RATON, FL 33431 RQUn.._ TOR TEL: (561) 994-2400 woter storage a wastewoter treatment solutions EXTERIOR TANK AIL to - a A. Exterior Sealer condition Overall, the exterior sealer fillets were in fair condition with more than 50% of the sealer having corroded. A total outside reseal of the seams is recommended at this time. The common root causes of the exterior sealer degradation are aging of the sealant and weathering from the elements. The sealer provides the coating protection for the panel edges and maintenance of the sealer fillet is critical to the extended life of the tank. As the sealer degrades, corrosion along panel edges may become evident. A maintenance re-caulk service should be performed as the exterior sheet edges become exposed. B. Exterior Glass coating condition The condition of the glass coating on the overall panel surface is good. No visible glass damage was noted. Care should be exercised around the tank to avoid future chips, such as chipping caused by stones thrown by mowing or other impact damage. Newly chipped glass should be touched up with Page 3 of 26 4722 N.W. BOCA RATON BLVD. FLORIDA AQUASTORE SUITE C-102 TANK INSPECTION REPORT BOCA RATON, FL 33431 fQU _n.. TORE TEL: (561) 994-2400 water storage a wastewater treatment solution, Manus Bond 75am sealant as soon as possible. The glass coating on the tank panels was in generally good condition. Pressure washing and minor touch ups in some areas is needed with sealer. C. Exterior bolts, bolt caps, accessories, and decals Bolts and bolt caps appear in good condition and no replacements are needed at this time. The bottom manway appears in good working condition, but the gasket needs replacement at this time. Ladders and associated accessories are in good condition and appear in good working order. The tank does not currently have a liquid level indicator or overflow pipe installed. Nozzles have rust forming on them and should be cleaned and coated with CIM. All decals should also be replaced. CO 1%- ILN %Ik‘ r-r. A '41111111,41. _..s- Page 4 of 26 4722 N.W. BOCA RATON BLVD. FLORIDA AQUASTORE SUITE C-102 _ TANK INSPECTION REPORT BOCA RATON, FL 33431 fQUn.. TORS TEL: (561) 994-2400 woter storope&wostewoter treatment solutions INTERIOR TANK D. Interior Sealer Condition Overall, the interior condition of the tank was in poor condition. The sealer on the interior of the tank has degraded more than 90%. The sealer provides the coating protection for the panel edges and maintenance of the sealer fillet is critical to the extended life of the tank. As the sealer degrades, corrosion along panel edges may become evident. A full maintenance re-caulk service using CIM should be performed as the interior sheet edges are exposed. • Li a f' 1 C- Y..r40 • . r o Page 5 of 26 4722 N.W. BOCA RATON BLVD. FLORIDA AQUASTORE SUITE C-102 TANK INSPECTION REPORT BOCA RATON, FL 33431 RQU _n.. TORE TEL: (561) 994-2400 woter storage a wastewoter treatment solutions • to 111110 • • • • z- Page 6 of 26 1.1 . 4722 N.W. BOCA RATON BLVD. FlORI I�� FLORIDA AQUASTORE SUITE C-102 _ TANK INSPECTION REPORT BOCA RATON, FL 33431 fQUn.. TORS TEL: (561) 994-2400 ...ter storope&wostewoter treatment solutions -—.. --wetlik, ,_._ ' ...wiiirtis.)viiifiN ........._ _......r.,01 ..wa jalimplIMMINIr .., _— r. . I to i ... 1:4 4' ` Ai A k\ om' K+ _ i. if •77.....-,- - f4r4 4 .....f- ^ram.-...,_ _ . . •.�lt ?'•�' 'kr, - . . - �'' T` _ Page 7 of 26 4722 N.W. BOCA RATON BLVD. FlORI I�11 FLORIDA AQUASTORE SUITE C-102 _ TANK INSPECTION REPORT BOCA RATON, FL 33431 fQUn.. TORS TEL: (561) 994-2400 ...ter storage&wostewoter treatment solution, E. Interior Glass Coating Condition of TANK The condition of the glass coating on the overall internal panel surface is in generally good condition. No visible metal loss was noted but the top horizontal seam has some rusting around the bolts and vertical seams which should be addressed. Newly chipped glass should be coated with CIM sealant as soon as possible. Pressure washing and minor touch ups in some areas as needed. f 4 •v• ) 3 • ��\�. ` '� . W.. 7^`-,�•Y •{J • ~ ; ,, �• ^_ as • to - • • - - Arr. • II I ,l r r t r III . • Page 8 of 26 co p rl�.r N m 0 z , OP C) 0O I . * r' • a) 1 N H U • • :� cn co + ,, _ -4., c .,, ..., .: ,:ip,,:. , . 11 ao ; a ~ —IZ s . Y w S 1 •+• _ �� ��. Z �, ti ,� H • i , I' ' ..1• ••! ' t� • . ,g• r y •A. -. ,,,, * --- - ,,;. 1,A,d, . f , / ' 1 . • C w o e = O E o d d O �� IA. cy II c Ai 4722 N.W. BOCA RATON BLVD. FLORIDA AQUASTORE SUITE C-102 TANK INSPECTION REPORT BOCA RATON, FL 33431 fQU _n.. TORE TEL: (561) 994-2400 woter storage a wastewoter treatment solution, F. Concrete Tank Floor Interior The interior concrete floor is in good condition with no cracks noticed. G. Roof Exterior The roof of the tank is a geodesic aluminum dome and appears in good condition. No repairs were noted for the roof walkway or guardrails. The sealer along the batten strips and around the gusset covers appeared in good condition with only 25% erosion noted. It is recommended that a full reseal of the exterior roof be completed within 6-8 years. The roof manway is in good working condition, but the seal tape between the hatch and base needs to be replaced immediately. The gravity vents are in good condition. There are two (2) electric roof ventilation fans that are not working and need to be replaced. to H. Cathodic Protection An inspection of the Cathodic Protection showed that the anodes are intact and do not appear to need replacement at this time. Page 10 of 26 4722 N.W. BOCA RATON BLVD. FLORIDA AQUASTORE SUITE C-102 TANK INSPECTION REPORT BOCA RATON, FL 33431 fQU _n.. TORE TEL: (561) 994-2400 water storage a wastewater treatment solutions RECOMMENDATIONS The tank needs to be resealed inside and out. The glass-fused-to-steel has handled the environment extremely well. We recommend the following service: • Power Wire brush clean and re-caulk all interior panel edge bolt seams with 2 component Urethane (CIM or equal) • Power Wire brush clean and re-caulk all exterior panel edge bolt seams with Manus Bond Sealer. • Exterior nozzles should be cleaned and recoated with two component urethane (CIM or equal) • Clean corrosion deposits and touch-up chipped glass on interior and exterior with urethane sealer as needed. to • Replace sidewall manway gasket • Replace 2 roof fans • Replace roof manway seal tape Following the maintenance service, a periodic tank maintenance plan should be followed to monitor the performance of the panel edge sealer fillets on the tank interior and exterior. By monitoring the performance of the sealer, whenever the sealer has reached the end of its serviceable life, either partial or complete reseal can be performed before metal loss especially along panel edges and bolt seams becomes significant, costly panel replacement can be avoided. Resealing of the panel edges and bolt seams when needed is critical to the continued structural integrity of the tank. We recommend that Florida Aquastore be employed to perform the continued inspection service at appropriate intervals. In typical applications such as this for the water storage service, the tank interior should be visually inspected every 5 years, more often for more aggressive and corrosive stored liquids. Page 11 of 26 4722 N.W. BOCA RATON BLVD. FtORI DR FLORIDA AQUASTORE SUITE C 102 TANK INSPECTION REPORT BOCA RATON, FL 33431 RQU _n.. TORE TEL: (561) 994-2400 woter storage a wastewoter treatment solutions Photo Addendum to Page 12 of 26 I. = 4722 N.W. BOCA RATON BLVD. FtORI DR FLORIDA AQUASTORE SUITE C 102 _ TANK INSPECTION REPORT BOLA RATON, FL 33431 RQU n.. TOR TEL: (561) 994-2400 ...ter storope&wostewoter treatment solutions Noillf, aA � 1, 4. Kiiiiii Ver 1 111111111 4' ---.--- — 41...... . I , 1 , . ; i1 i1 . t. ,41 it ,,, . .! to 4 4aiii ,4k _•,,,4 0.r. 4 f Page 13 of 26 1.1 = 4722 N.W. BOCA RATON BLVD. r10R1 DO1 FLORIDA AQUASTORE SUITE C-102 TANK INSPECTION REPORT BOCA RATON, FL 33431 RQUE TORE TEL: (561) 994-2400 woter storoae&wastewater treotment solutions .r.s.•wF9ee.•ti'.,'. $ l \i'4, 77 ` Br s, III 0 a 0 MIN MN/ ; ,----r- 1 '' i r 1 illw Illjr t 1 lir Page 14 of 26 4722 N.W. BOCA RATON BLVD. nOR'D fl FLORIDA AQUASTORE SUITE C 102 TANK INSPECTION REPORT BOCA RATON, FL 33431 RQUE TOR TEL: (561) 994-2400 woter storoae&wastewater treotment solutions • • • • . *alp Off v • ^Y- T - .. � Page 15 of 26 1.1 = 4722 N.W. BOCA RATON BLVD. FlORI I�I1 FLORIDA AQUASTORE SUITE C-102 BOCA RATON, FL 33431 RQU _n.. TANK INSPECTION REPORT TOR TEL: (561) 994-2400 water storage&wastewater treatment solutions i I - t 4 . , , /// (/, i MN ----__ . 1 1' ,. - • ii..7.714.. ma :- t . , ... , A ' i, ll Illy l'' TI,PE-rAiwrmon. II :.... . - • ■1 . . ,,.. ..,.,,,.,, • • • • `/ -.• 1. • II. ill...7i I , .. .. • 4,... ,,,_ • 101 1 , . . .. •1 .,t - .. • .1 °, ... . , `,: —, r_ „r ,,,,_ ., .. 113 i A. O • ..1 ii- _ .S Page 16 of 26 M .._ 4722 N.W. BOCA RATON BLVD. FtORI DR FLORIDA AQUASTORE SUITE C-102 TANK INSPECTION REPORT BOLA RATON, FL 33431 RQU _n.. TORE TEL: (561) 994-2400 woter storage a wastewoter treatment solutions a , 1 !.. Ilii . r t 0 M'I/ { rt I • . 4, Page 17 of 26 4722 N.W. BOCA RATON BLVD. ��O�I�� FLORIDA AQUASTORE SUITE C-102 _ . TANK INSPECTION REPORT BOCA RATON, FL 33431 RQU n.. TOR TEL: (561) 994-2400 woter storope S wostewoter treatment solutions 744k- 4111 1441111111 441 ili4k _ _t fl 1 10 spii",14,* • ii 1, tiliii, 461mirmisiiimewi is I 4% 4% 4k k -4k ik— (-40 .4k, 4k ' 41/4441111.4 4064......._ )(.4}4.,„,,, . l' ir • . ,► 1r 1 ' E Page 18 of 26 ■ = .._ 4722 N.W. BOCA RATON BLVD. FtORI DR FLORIDA AQUASTORE SUITE C-102 TANK INSPECTION REPORT BOLA RATON, FL 33431 RQU _n.. TORE TEL: (561) 994-2400 woter storage a wastewoter treatment solutions r 1i�'t t i.111 .. 1 `t Illt w ( r '',:- . •:-7- .' - 407 410 : . • M toell'k . _ .. 1 t . .. . , .., . , . .... . , T:,, Y _ , ,. .„ ... - iii„,„4,,,... , , , , ., . • ' f la 7 / . J,40' “`'.. • 'AM, rl i�r h4, rr J , . ,, )1 :0.1, , iv 1 IN!1466.' tiC ' Page 19 of 26 1.1 M 4722 N.W. BOCA RATON BLVD. FlORI DR FLORIDA AQUASTORE SUITE C-102 TANK INSPECTION REPORT BOLA RATON, FL 33431 RQU _n.. TORE TEL: (561) 994-2400 woter storage a wastewoter treatment solutions • Alli ,.'PP r 011e ,,.,.z , .l 1 , .,4 firgi. 1, 1 „41-Egir,. ...._. - . r./: . ,L ,,... . . No to , ...„...... , wildj e. ram. , _ �trr� i l. I *ft • • if 1 1 .t it I may_ Page 20 of 26 1.1 4722 N.W. BOCA RATON BLVD. FLORIDA AQUASTORE SUITE C-102 _ TANK INSPECTION REPORT BOCA RATON, FL 33431 fQUn.. TORS TEL: (561) 994-2400 woter storope&wostewoter treatment solutions f 1141111110110 • Ail• • • • tO • • • • A t fir _ ;CI!• 31j 1 r:=„0. . Page 21 of 26 1.1 = 4722 N.W. BOCA RATON BLVD. FlORI I�I1 FLORIDA AQUASTORE SUITE C-102 TANK INSPECTION REPORT BOCA RATON, FL 33431 RQU _n.. TOR TEL: (561) 994-2400 woter storage a wastewoter treatment solutions /M i ! • , • r • s • +. • .' SI • ' s . • . ilift- . . ' .(' • , ) ,. to • 4 . , • • • . • • Page 22 of 26 1.1 = 4722 N.W. BOCA RATON BLVD. FlORI DI1 FLORIDA AQUASTORE SUITE C-102 _ TANK INSPECTION REPORT BOCA RATON, FL 33431 RQU n.. TOR TEL: (561) 994-2400 woter storage&wastewoter treatment solutions -.. ' • \. ` \\\,. J., a ` r ` ^ I" •: wv y T+. SJ•� • r - 7 • 4. 5 0111, .,:...,.,; t , • IVillibik l . , Page 23 of 26 1.1 4722 N.W. BOCA RATON BLVD. FIORI DR FLORIDA AQUASTORE SUITE C 102 TANK INSPECTION REPORT BOLA RATON, FL 33431 RQUE TOR TEL: (561) 994-2400 woter storoae&wastewater treotment solutions 111111 ` . t 11111 '11HILI1111-1414141411414 11111/"":1111111/4NN44441114.141141111111\6 4 -011111.111.11 to it f � Page 24 of 26 1.1 = 4722 N.W. BOCA RATON BLVD. F I(I IO1 FLORIDA AQUASTORE SUITE C 102 _ TANK INSPECTION REPORT BOLA RATON, FL 33431 RQUnw TORS TEL: (561) 994-2400 water storo0e&wastewater treotment solutions 1 461 tO IIIIM%diL.. mar Page 25 of 26 1.1 4722 N.W. BOCA RATON BLVD. F10R1 uO1 FLORIDA AQUASTORE SUITE C-102 _ TANK INSPECTION REPORT BOCA RATON, FL 33431 RQUnw TOR TEL: (561) 994-2400 woter storo0e&wastewater treotment solutions J fit • ..000000001 tO Page 26 of 26