HomeMy WebLinkAboutCA Brooks Building Solutions Supplemental Agreement 4 Electrical Equipment for GP and PC EXECUTIVE SUMMARY
AGENDA ITEM:
Proposed Supplemental Agreement No. 4 to Continuing Services Contract RFQ 2020/2021-A17 with
Brooks Building Solutions, Inc. (Brooks) for Prepurchase of Electrical Equipment for the Governor's
Park Lift Station, Governor's Park Reclaimed Water Pump Station, and Peter's Creek Water
Reclamation Facility Project.
Date: September 29, 2022
BACKGROUND:
CCUA staff requests approval from the Board of Supervisors to execute Supplemental Agreement No.
4 with Brooks for the pre-purchase of electrical equipment for the Governor's Park Lift Station,
Governor's Park Reclaimed Water Pump Station, and Peter's Creek Water Reclamation Facility
Project. This equipment consists of the Motor Control Centers, Switchgear and Automatic Transfer
Switch to power these facilities. The electrical equipment is the longest lead time equipment for these
facilities,with an expected delivery time of sixty(60)or more weeks from the time the order is placed.
This equipment is being purchased through CCUA's Continuing Contract RFQ 2020/2021-A17 with
ca
c Brooks Building Solutions Electrical Troubleshooting, Repair, and Installation. Per the Contract,
:' CCUA may purchase new electrical or control equipment to support projects from CCUA Engineering
0 or Maintenance Departments.
c
= BUDGET AND DELIVERY:
II
cc
Pricing provided by Brooks for the pre-purchase equipment is listed below:
Governor's Park Lift Station Project $205,090.00
Governor's Park Reclaimed Water Pump Station $251,587.00
Project
Peter's Creek Water Reclamation Facility $939,387.00
Project
The current Engineers Estimate of Probable Construction Costs is approximately $45 million. The
engineer of record provided the equipment details to the vendor and has reviewed it for accuracy. Staff
reviewed the quote for reasonableness and negotiated terms with Brooks. Funds will be drawn from
the Governor's Park Capital Improvement Plan Budget. Equipment is not expected to be available
until after the electrical buildings are in place. Accordingly, staff expects equipment will be offloaded
FOB directly to its point of installation.
RECOMMENDATION:
Staff respectfully requests the Board of Supervisors' approval of the attached Supplemental Agreement
No. 4 to the Continuing Services Contract RFQ 2020/2021-A17 with Brooks Building Solutions,Inc.,
for the electrical equipment needed for Governor's Park Lift Station, Governor's Park Reclaimed
Water Pump Station, and Peter's Creek Water Reclamation Facility Project in the amount of
$1,392,441.00.
ATTACHMENTS:
Supplemental Agreement No. 4
Scope of Work and Fee Proposal
Supplemental Agreement No. 4 to Continuing Services Contract RFQ 2020/2021-A17 with
Brooks Building Solutions for Pre-Purchase of Electrical Equipment for the Governor's Park Lift
Station,Governor's Park Reclaimed Water Facility,and Peter's Creek Water Reclamation Facility
Project.
Engineer: Brooks Building Solutions, Inc. Owner: Clay County
4501 Beverly Avenue Utility Authority
Jacksonville, Florida 32210
Date: October 4, 2022
Item Description of Services
Contractor's quote dated September 29, 2022, for $ 201,467.00
Governor's Park Lift Station Project
Contractor's quote dated September 29, 2022, for $251,587.00
Governor's Park Reclaimed Water Pump Station Project
Contractor's quote dated September 29, 2022, for Peter's $939,387.00
Creek Water Reclamation Facility Project
Total Lump Sum Price Not to Exceed Without Prior Authorization $ 1,392,441.00
The Contract time shall commence on the needed date. This document, along with the attached
scope and fee proposal dated September 29, 2022, shall become an amendment to the existing
Agreement for Electrical Troubleshooting, Repair, and Installation RFQ 2020/2021-A17 dated
November 1, 2021. All provisions, terms and conditions of the existing Agreement will apply to
this Supplemental Agreement.
Accepted by: Date:
Contractor:
H. Neff Jenkins
President
Brook Building Solutions, Inc.
Accepted by: Date:
Owner:
Jeremy Johnson, P.E., MBA
Executive Director
Clay County Utility Authority
S Brooke
Building Solutions
PROPOSAL
Clay County Utility Authority September 29, 2022
Project-Governors Park WWLS
3176 Old Jennings Road
Middleburg, Florida 322068
Attention: Paul Stelnbrecher
We propose to furnish the following equipment and services for the above referenced project.
Brooks Building Solutions standard TERMS AND CONDITIONS apply to this proposal and price
quotation,with the EXCEPTION for this Project Only: Terms of Payment, Net 5 days, Mark up for
Equipment reduced from 25%to 10%.
This Proposal Includes:
Providing Eaton Engineering Services/Equipment/Submittals for the Governors Park WWLS Project, Rev. B
ONLY.
• Provide Submittals/Drawings from Eaton Manufacturing
• Provide Factory Start Up for Eaton MCC Equipment as shown in the bill of material, see attached.
• Provide Eaton Motor Control Centers, as per bill of material, see attached.
to • Provide Enclosed Circuit Breakers, as per bill of material, see attached.
• Provide Eaton Manufacturing 3-year Warranty, see attached.
• All orders must be released for manufacture withing 90 days of date of order. If approval drawings are
required, drawings must be returned approved for release within 60 days of mailing. If drawings are not
returned accordingly, and/or if shipment is delayed for any reason, the price of the order will increase
by 1.0% per month or fraction thereof for the time the shipment is delayed.
• Seller shall not be responsible for any failure to perform, or delay in performance of, its obligations
resulting from the COVID-19 pandemic or any future epidemic, and Buyer shall not be entitled to any
damages resulting thereof.
Exclusions and Conditions of This Proposal:
• Brooks Building Solutions, Inc. will not be held responsible for any damaged equipment, equipment lost
after it has been received.
• Brooks Building Solutions, Inc. will not be responsible for any changes or delays for this Equipment
purchased. Lead Time are projected dates and cannot be Guaranteed.
• Any Price Increase from the Manufacture will Result in a Change Order for Price Increase.
• Any additional Equipment needed will be purchase with an Approved Change Order approved by
CCUA.
• Components or labor for items deemed necessary but are not included in the original scope of work will
be considered an extra cost to project and will only be performed with the expressed authorization of
the customer and invoiced to the customer at the non-contract customer labor rate.
Papa 1 ol'3
Corporate 14501 Beverly Avenue!Jacksonville.FL 322101 P 904.6423303 1 F 904.641.8722
Tallahassee 12815-1 Industrial Plaza Dr.1 Tallaheaecc,FL 32301 1 P 850.701,23501 F 850.701.2355
Il:C'A C1I59739 UVAC RQUIIMJIiNC IIiUII DENGAU1t1►IATl1N I IiNIAILIY&)I.UCIf1NN I NtstVICI, I PARIN UA:CN 21N9RA
20)L UI
• This proposal is only valid for thirty (30)days from the date of issue.
• Full freight Is allowed, and all applicable taxes are Included,
Proposed Price:
Two Hundred One Thousand Four Hundred Sixty-Seven and 00/100 Dollars-$201.467.00
TERMS AND CONDITIONS
This agreement is subject to the TERMS AND CONDITIONS included in this Proposal
Sro• 8uildln =olutlons, Inc. Clay County Utility Authority
Jeff Hendricks
Senior Project Manager
Date: September 29, 2022 Date:
to
Page 2.c'3
Cotponic F 4501 Beverly Avenue I Jacasonvlllc.FL 32210 I P 904.64233031 F 904.641.8722
Tollahaas c 12815-I lndunriel Plum Dr.I Tallahassee.FL 32301 IP 850.70113501 F 850.7011355
1.1:CA COSMO HVAl'IulCIIMHWC1 BUII.131NU AU111MA11UN I I:NIIRUYStli.U1111NeIKhI 'KI I Mum UA:CNMOM
20111.116.111
Detail Bill of Material ,,
as Project Neme: CCUA Governors Park RWPS and Negotiation No: JV730927X2K2
&linesnWbrrtvida WW LS
General Order No: Alternate No: 0003
Item No. Qty Product Description
1 Engineering Services Start-Up
Start-Up
Designation Start-Up
item No. Qty Product Description
1 Engineering Services NSP2
Designation Spare Parts
item No. Qty Product Description
1 EESS Services EESS Short Circuit and Coordination Studies:Arc Rash Hazard
Analysis,PE Review/Stamp Required-Florida
"""See Approval Drawings for Clarifications and Exceptions""
Daniel Griffin
Designation Study
Qty List of Materials
to 1 ESS Study-BidManager
1 2 Weeks Lead Time for Data Request Submittal
1 4-6 Weeks Lead Time for Study Completion
1 Quoted by Bld Manager
1 PE Review Stamp Required(Florida)
1 Arc Flash study
Item No. Qty Product Description
1 Motor Control Centers 60 Hz,Class 2B wiring,480V 3-Phase Service,65,000 Bracing,
Short Circuit Rating,Bottom Incoming,NEMA 1 Gasketed 21"
Front Mt Only enclosure,800A Copper Main Horizontal Bus,No
Neutral,Main Breaker.Used X-Space:53,Blank X-Space:7,
Future X-Space:0,MCC Lead Time Code:U.
Designation MCC-1
Qty List of Materials
1 PXM2270 METER/DISPLAY 60HZ 5A 90-265V AC/DC
1 HMDL Main Bkr(600A trip),Lugs:3-#3/0-400KanU
1 PXM2270
2 600V Potential transformer
3 800A Current transformer
2 DG1 VFD,Constant torque,140 FLA,480V,HMCP
1 HFD Bkr(30A trip)
2 #14awg SIS Control Wire
2 3 Pos,Sel.Sw.,E34(Hand-Off-Auto)
2 Terminal Block-Latching Pull-Apart,Std.
Detail Bill of Material f g�: i of
EIT•N Project Name: CCUA Governors Park RWPS and Negotiation No: "N730927X2K2
Pawing WW LS
General Order No: Alternate No: 0003
Qty List of Materials
2 Wiremarkers al Each End
2 3 x DI,3 x D0,1 x thermistor,24 Vdc/EXT option card
2 SIS Power Wire
2 Panel Elapsed Time Meter(Standard)
2 1 x AI,2 x AO(isolation to control board)option card
2 DG1 Dv/Dt Output Filter-FR5
2 Coil Surge Suppressor
2 Pilot Light-E34-LED(Overload Trip)
1 Description not available
2 Pilot Light-E34-LED(On,Run,Fast,Forward)
8 C-H Model D7,300V,3 Pole Socket Relay
2 Speed Pot 1000 Ohm
2 Blank Device Panel
2 Pilot Light-E34-LED(Off,Stopped)
1 30 Kva 3 ph,440-480V/120-208V High Efficiency Xfmr,50A PH.,110A
Sea Bkr.
1 PL1A Panelboard 225A 120/208V 3PH 4W 42 CKT
42 Pnlbd Bkr,BAB 1 Pole 20A bkr
1 100KA,SPD Standard+Surge Counter Features Package,with Circuit
Breaker
1 300KA,SPD Standard+Surge Counter Features Package,with Circuit
Breaker
3 12"Door
1 6'Door
1 Thermostat-for enclosure space heater control
1 Rodent Barriers both skies
1 1200A Vertical Bus(Tin-plated cu)
5 65KA Bus Bracing
to 5 300A Herd,Cu Gnd Bus, 1/4"x 1"Bar
5 Bottom Vertical Bus Barrier
1 2B Wiring
5 Structure Floor Leveling Channel Sills
5 Fire Wall Bafflers between each section
4 600A Vertical Bus(Tin-plated cu)
5 Labyrinth,Isolated/insulated vertical bus barrier with shutters
5 Tin Plated horizontal bus
5 800A Copper Fmt Mtd 21"NEMA 1 Gasketed
1 CONTROL RELAYS WHERE APPLICABLE TO BE EATON D3 TYPE.
EXCEPTION FOR'RR'IN WELL PUMP DUE TO CONTACT
REQUIREMENTS,
1 DIVERSIFIED SLD SERIES 3 PHASE VM IS TO BE MOUNTED IN
METERING UNIT
1 METER TO BE PXM 2280
Item No. Qty Product Description
1 Enclosed Circuit Breaker Enclosed Breakers
Catalog No WNNGH308036E-FLX
Designation S.E.MCB
Catalog No Qty List of Materials
WNNGH308036E- 1 Factory Assembled Enclosed Nitric)RMS 310+Circuit Breaker
FLX
NGH308036E 1 Circuit Breaker Frame and Trip unit
WNDN1200 1 Circuit Breaker Enclosure-Nema 4X,Stainless
DSBOONK 1 Enclosure Neutral Kit
CN33819 1 Enclosure to be 316 grade SS.
E mail .N Detail Bill of Material do rr of
Project Name: CCUA Governors Park RWPS and Negotiation No: JV730927X2K2
Powering Business Worm W W LS
General Order No: Alternate No: 0003
Catalog No Qty List of Materials
CN293 1 .21
Eaton Selling Policy 25-000 applies.
All orders must be released for manufacture within 90 days of date of order entry. If approval drawings are required,drawings must be returned
approved for release within 60 days of mailing. If drawings are not returned accordingly,andlor if shipment Is delayed for any reason,the price of the
order will increase by 1.0%per month or fraction thereof for the time the shipment Is delayed.
Seiler shall not be responsible for any failure to perform,or delay in performance of,Its obligations resulting from the COVID-19 pandemic or any
future epidemic,and Buyer shall not be entitled to any damages resulting thereof.
to
MCC General Information
MCC General information Ind.Light Type 6v Xfmr
Wring Diagram Type Eaton Standard PL Color(On) Red n
MCC Quantity PL Color(Off)
Gre
Standards UL845,NEMA,NEC PL Color(O.L,Trip) Blue
Special Codes UL Structure Schedule
Service Voltage(3 Phase) 480
Frequency 60 There are 5 structure(s).
System 3PH3W Structure(s)1 have a 1200 A Vertical Bus.
Witness Testing No Structure(s)2,3,4,5 have a 600 A Vertical Bus.
Total width of all sections la 104"
Enclosure Specifications Height of all sections Is 91"
Total Structures 5 Unit Modifications1 Gasketed
Depth 21"Front Mt Only Iltl4awg SIS Control Wire
Height 90" Terminal Block-Latching Pull-Apart,Std.
Horizontal Wreways 9"High,Top&Bottom Wremarkers at Each End
Vertical Wreways 4" Coll Surge Suppressor
Channel Sills Yes SIS Power Wre
Bottom Plates None
150 Watt Space Heaters No
Space Heater Thermostat 1
Master Terminal Block Location None
IBC/CBC Seismic Qualified No
ABS Certified No
Bus System Specifications
Main Bus Amps 800
Main Bus Material Copper
Main Bus Bar Plating fin
Insulated Horiz.Bus No
1000A1sq In.Cu Bus No
Vertical Bus Amps See Structure Schedule
Vertical Bus Material -fin Plated Copper
Vertical Bus Barrier Labyrinth,Isolated/
Insulated with shutters
to Bus Bracing 65,000
Ground Bus 300
Ground Bus Location Top
Ground Bus Lug Size 1-#6-350Kcmil
Ground Bus Lug Type Screw
Plug-in 300A Vert.Grid.Bus No
Neutral None
Horizontal Bus Temperature Rise 85 deg C
Bottom Vert.Bus Barrier Yes
Vertical Ground Bus No
Incoming Line Termination
Device:HMDL Main Bkr(600A trip),Lugs:3-#3/0-400Kcmll
Cable Entry Bottom
Splice Kit I Transition None
MCC Type Match Up
MCC Type Match Lip GO# "None**
MCC Starter Specifications
Wring Class 2B
Control Voltage 120
Control Voltage Src Ind CPT
Nameplate Size 1"X 2.5"
Nameplate Color Black/White Letters
Pilot Dev.Model E34
The Infomutlon on this document Is PREPARED BY DATE
created by Eaton Corporation.Its Denial onlnn 912E12022 Eaton Fayetteville, NC
disclosed In confidence and It Is only to APPROVED pA doe NAPE CCl1A Governors Perk RYVPS and NAN LS
be used for the purpose 1n which R Is
supplied. DESIGNATION MCC-1
VERSION TYPE DRAWING TYPE
1,0.2.8 Freedom+MCC Customer Appr.
NE0.ALT Numbs REVISION DING SIZE O.O. rrau SHEET
JY771210-0o03 _ A 1 of 6
Notes/Special Instructions
CONTROL RELAYS WHERE APPLICABLE TO BE EATON D3 TYPE. EXCEPTION FOR"RR"IN WELL PUMP
DUE TO CONTACT REQUIREMENTS.
DIVERSIFIED SLD SERIES 3 PHASE VM IS TO BE MOUNTED IN METERING UNIT
METER TO BE PXM 2280
to
The Information on this document le PREPARED BY DATE
created by Eaton Corporation.It Is Daniel Griffin 9128/2022 Eaton Fayetteville, NC
disclosed In confidence and It Is only to
be used for the purpose In which It la APPROVED BY DATE JOB NAME CCUAGovemors Perk RWPS and MI LS
eupplled. DEsioNATIDN MCC-1
VERSION TYPE DRAIMNO TYPE
1.0.2.8 Freedom+MCC Customer Appr.
•
NEO-ALT Motet.t REVISION MVO SIZE OD. ITEM SHEET
JVr80927X21.20063 A 2 015
•
Top View
_
5.41 5.�41 5.41 5.41 5.41
r '""1 Ti> 21. ( l k•) , TT.
5F 4F 3F 2F IF
•
A 42CKT A_..-__
B DG1 Drive DG1 Drive SPD
FR5 FR5
C 140A CT 140A CT eee
D SPD
E II til
F
G Ii I MTR
! ,
H 31
J HFD3030
K
to L
M 30KVA !HMDL3600
20.15o n 20 078 1 24.078 420.078 2 c,.n7,= fl
1.25 1.25 1.25 1.25 1.25
-F -f -F -304r- -F
0A
N co 1.25 1.25 1.25 1.25 1.25
20.158 20.078 24.078 20.078 20.078
Floor View
The Information on this document la PREPARED E' DATE
created by Eaton Corporation.It to Daniel Griffin er2ar2022 Eaton Fayetteville,NC
disclosed in confidence and it le only to •
be used for the purpose In which It le APPROVED BY DATE JOB NAIAE CCUA Governors Perk RWPS Ind WW LS
supplied. DESIGNATION MCC•1
VERSION TYPE MIMING TYPE
1.0.2.8 Freedom+MCC Customer Appr.
NEG-ALT Numbs REVISION DlhO 8 E O.O. rim SHEETJw3ot2Tx .000 A _ 3 or 3
Una Nam=kg Deacrfotlon Class Starter Size filsati1�
HPJFLA aka Features
1512.Disc. pang
5M RWPS Del VFD,Constant HMCP 1 Blank Device Panel
HSP NO.2 torque, 140 FLA, 100/140 3P 1 Speed Pot 1000 Ohm
480V,HMCP NONE ' 160 4 C-H Model D7,300V,3 Pole Socket
Relay
1 Pilot Light-E34-LED(On,Run,
Fast,Forward)
1 Pilot Light-E34-LED(Off,Stopped)
1 Pilot Ught-E34-LED(Overload
Trip)
1 Panel Elapsed Time Meter
(Standard)
1 3 Pos.Sel.Sw.,E34(Hand-Off-
Auto)
1 3 x DI,3 x DO,1 x therrnIstor,24
Vdc/EXT option card
1 1 x AI,2 x AO(isolation to control
board)option card
1 DG1 Dv/Dt Output Filter-FR5
4M RWPS DG1 VFD,Constant HMCP 1 Blank Device Panel
HSP NO.1 torque, 140 FLA, 100/140 3P 1 Speed Pot 1000 Ohm
480V,HMCP NONE 150 4 C-H Model D7,300V,3 Pole Socket
Relay
1 Pilot Ught-E34-LED(On,Run,
Fast,Forward)
1 Pilot Light-E34-LED(Off,Stopped)
1 Pilot Light-E34-LED(Overload
Trip)
1 Panel Elapsed Time Meter
(Standard)
1 3 Pos.Sel.Sw,E34(Hand-Off-
Auto)
1 3 x DI,3 x DO,1 x thermistor,24
Vdc/EXT option card
1 1 x Al,2 x AO(isolation to control
to board)option card
1 DG1 Dv/Dt Out;ut Filter-FR5
3F PANEL L7 PL1A Panelboard 42 Pnlbd Bkr,BAB 1 Pole 20A bkr
225A 120/208V 3PH
4W 42 CKT 5A10398.DWF
3M T-L1 30 Kva 3 ph,440-480
/120-208V High
Efficiency Xfmr,50A Pri., 5A10398.DWF
110A Sec.Bkr.
2B PANELBOARD 2D
2f3
100KA,SPD Standard
+Surge Counter
Features Package,with NONE
Circuit Breaker
300KA,SPD Standard
+Surge Counter
Features Package,with NONE
Circuit Breaker
PXM2270
NONE
2J HYPO ROOM HFD Bkr(30A trip) HFD
UNIT HEATER 3P
5599A85.DWF 30
2L 12"Door
2M 6"Door
1 B 12"Door
1D 12"Door
The Information on this document Is j PREPARED BY DATE
meted by Eaton corporation.It is Daniel Griffin 9/28/2022 Eaton Fayetteville,NC
disclosed In confidence end it is only to
be used for the purpose in which It Is APPROVED BY DATE JOE NAME CCUA Governors Park RWPS and WW LS
supplied. _ _ DESIGNATION MCC-1
VERSION TYPE DRAWING TYPE
1.0.2.8 Freedom+MCC Customer Appr.
NEG-ALTNumbw REVISION DWG SIZE G.O. ITEM SHEET
,rvr30e27x1x2.00o3 A 4 of a
Unit NamWe Dee 10 tpn Masa Starter Size lalsafte Walt
HPLELA Piles Mums.
Wire Dlag, Trip/CIIR
1 M HMDL Main Bkr ECouA HMDL 1 Description not available
trip),Lugs:343/0- 3P
43/0-400Kcmil 5599A92.DWF 800
tO
The Information on this document is PREPARED BY DATE
crested by Eaton Corporation.It Is Daniel Griffin sai 2022 Eaton Fayetteville,NC
disclosed In confidence and It Is only to
be used for the purpose In which it Is APPROVED BY DATE .roe RArIE CCUAOowrnors Park RAPS and WW LS
supplied. DBSIONATION MCC-1
—
MOWN TYPE 'DRAWING TYPO
_ 1.02.11 Freedom+MCC CuatomerAppr.
NE6ALTHumGr REVISION DWG WE D. ITEM 1 SHEET
NTH i27)f2X2.0003 A 5 of 6
S Brooks
Building Solutions
PROPOSAL
Clay County Utility Authority September 29,2022
Project-Govemors Park RWPS
3176 Old Jennings Road
Middleburg,Florida 322068
Attention: Paul Steinbrecher
We propose to furnish the following equipment and services for the above referenced project.
Brooks Building Solutions standard TERMS AND CONDITIONS apply to this proposal and price
quotation,with the EXCEPTION for this Project Only: Terms of Payment, Net 5 days, Mark up for
Equipment reduced from 25%to 10%.
This Proposal includes:
Providing Eaton Engineering Services/Equipment/Submittals for the Governors Park RWPS Project Rev.3
Bill of Material ONLY.
• Provide Submittals/Drawings from Eaton Manufacturing, as shown in the bill of material, see attached.
• Provide Factory Start Up for Eaton MCC Equipment as shown in the bill of material, see attached.
• Provide Eaton Motor Control Centers, MCC-MAIN, MCC 1, as per bill of material, see attached.
to • Provide Eaton Manufacturing 3-year Warranty, see attached.
• All orders must be released for manufacture withing 90 days of date of order. If approval drawings are
required, drawings must be returned approved for release within 60 days of mailing. If drawings are not
returned accordingly, and/or if shipment is delayed for any reason, the price of the order will increase
by 1.0% per month or fraction thereof for the time the shipment is delayed.
• Seller shall not be responsible for any failure to perform, or delay in performance of, its obligations
resulting from the COVID-19 pandemic or any future epidemic, and Buyer shall not be entitled to any
damages resulting thereof.
Exclusions and Conditions of This Proposal:
• Brooks Building Solutions, Inc. will not be held responsible for any damaged equipment, equipment lost
after it has been received.
• Brooks Building Solutions, Inc. will not be responsible for any changes or delays for this Equipment
purchased. Lead Time are projected dates and cannot be Guaranteed.
• Any Price Increase from the Manufacture will Result in a Change Order for Price Increase.
• Any additional Equipment needed will be purchase with an Approved Change Order approved by
CCUA.
• Components or labor for items deemed necessary but are not included in the original scope of work will
be considered an extra cost to project and will only be performed with the expressed authorization of
the customer and invoiced to the customer at the non-contract customer labor rate.
• This proposal is only valid for thirty(30)days from the date of issue.
• Full freight is allowed, and all applicable taxes are included.
P.gc I 01'3
Corporate 1450I Bcvcrty Avrnuc I3.cicsanvi]In.FL 32210I P 904.642.3303 I F 904 641 8722
Tallahsaacc 12815-I Industrial Plaza Dr.I Tall.hesacc.FL 32301 I P 850.701.23501 F 850.701.2355
H.CA(INN71V IIVACId)Ull4HI5Sfl IIIJUIINU AU11I.IA'LION I IINIJ4UY!NA U r1ONN I NAVK'h I PAR114 W.CN 3106116
31I a.e6.01
Proposed Price:
Two Hundred Fifty-One Thousand Five Hundred Ei ht•Seven and 00/100 Dollars-$251,587.00
TERMS AND CONDITIONS
This agreement is subject to the TERMS AND CONDITIONS included in this Proposal
oks Bulldlnol ns,Inc. Clay County Utility Authority
Jeff Hendricks
Senior Project Manager
Date: September 29. 2022 Date:
to
Pip 2013
Corporate 14501 Beverly Avenue I Jacksonville,FL 32210 I P 904.642 5303 I F 904.641.8722
Tallahassee 12815-1 Industrial Plaza Dr.I Tallahassee,FL 32301 I P 850.701.2350 F 850.701,2355
I•l:CA COMM IIVAC'N,/La M NI 111UIL 111NU AUR,MAION IFNIItUY St RUTH/NS SIIRVICR I PARTS UA:CN 2IY*Ia
a111 a.OR01
E LDetail Bill of Material a e at
JV Project Name: CCUA Governors Park RWPS and Negotiation No: 730927X2K2
Poore ticg 8usw►9ss 14)rldwkde W W LS
General Order No: Alternate No: 0002
Item No. Qty Product Description
1 Engineering Services Start-Up
Start-Up
Designation Start-Up
Item No. Qty Product Description
1 Engineering Services NSP2
Designation Spare Parts
Item No. Qty Product Description
1 EESS Services EESS Short Circuit and Coordination Studies:Arc Flash Hazard
Analysis,PE Review!Stamp Required-Florida
"See Approval Drawings for Clarifications and Exceptions`'
Daniel Griffin
Designation Study
Qty List of Materials
1 ESS Study-BidManager
to 1 2 Weeks Lead Time for Data Request Submittal
1 4-8 Weeks Lead Time for Study Completion
1 Quoted by Bid Manager
1 PE Review Stamp Required(Florida)
1 Arc Flash study
Item No. Qty Product Description
1 Motor Control Centers 60 Hz,Class 28 wiring,480V 3-Phase Service,65,000 Bracing,
Short Circuit Rating,Bottom Incoming,NEMA 1 Gasketed 21'
Front Mt Only enclosure, 1200A Copper Main Horizontal Bus,No
Neutral,Main Breaker.Used X-Space:18,Blank X-Space:6,
Future X-Space:0,MCC Lead Time Code:U.
Designation MCC-MAIN
Qty List of Materials
1 NGH-C Main Bkr(1200A trip),Lugs:4-#1/0-750Kcmil
1 Service Entrance Label
1 Main Bkr Shunt Trip
1 RMS 310+ALSIG Trip wl GF
1 300KA,SPD Standard+Surge Counter Features Package,with Circa
Breaker
3 12'Door
1 Thermostat-for enclosure space heater control
2 Structure Floor Leveling Channel Sills
2 Fire Wall Bafflers between each section
2 600A Vertical Bus(Tin-plated cu)
Detail Bill of Material a 2 c�
F . Project Name: CCUAL Governors Park RWPS and Negotiation No: JV730027X2K2
Powering Business Worrdwrbte WW LS
General Order No: Alternate No: 0002
Oty List of Materlais
1 Rodent Barriers both sides
1 2B Wiring
2 Bottom Vertical Bus Barrier
2 Labyrinth,Isolated/Insulated vertical bus barrier with shutters
2 600A Hord.Cu Gnd Bus,1/4'x 2'Bar
2 65KA Bus Bracing
2 Tin Plated horizontal bus
2 1200A Copper Fmt Mtd 21'NEMA 1 Gasketed
1 #2-600 Kcmli 4/Ph Sub Feed Lugs(Screw)
1 CONTROL RELAYS WHERE APPUCABLE TO BE EATON D3 TYPE,
1 MCB ARMS Switch to be on front of door.
Item No. Qty Product Description
1 Motor Control Centers 60 Hz,Class 2B wiring,480V 3-Phase Service,65,000 Bracing,
Short Circuit Rating,Bottom Incoming,NEMA 12 Dust tight 21'
Front Mt Only enclosure,1200A Copper Main Horizontal Bus,No
Neutral,Main Lugs.Used X-Space:52,Blank X-Space:8,Future
XSpace:0,MCC Lead Time Code:U.
Designation MCC-1
Qty List of Materials
1 PXM2270 METER/DISPLAY 60HZ 5A 90-265V AC/DC
1 #2-600 Kcmil 4/Ph Main Lugs(Screw)&CTs
1 PXM2270
2 BOOV Potential transformer
3 100A Current transformer
2 DG1 VFD,Variable torque,261 FLA,480V,HMCP
1 HFD Bkr(20A trip)
2 Terminal Block-Latching Pull-Apart,Std.
2 3 Pos.Sel.Sw.,E34(Hand-Off-Auto)
2 #14awg SIS Control Wire
2 SIS Power Wire
2 Coil Surge Suppressor
2 Panel Elapsed Time Meter(Standard)
2 DG1 Dv/Dt Output Fitter-FR6
2 3 x DI,3 x DO,1 x thermistor,24 Vdc/EXT option card
2 Wiremarkers at Each End
2 Pilot Light-E34-LED(Overload Trip)
2 Speed Pot 1000 Ohm
2 Pilot Light-E34-LED(On,Run,Fast,Forward)
8 C-H Model D7,300V,3 Pole Socket Relay
2 1 x Al,2 x AO(isolation to control board)option card
2 Blank Device Panel
2 Pilot Light-E34-LED(Off,Stopped)
1 30 Kva 3 ph,440-480V/120-208V High Efficiency Xfmr,50A Pri.,110A
Sec,Bkr,
1 PL1A Panelboard 225A 120/208V 3PH 4W 42 CKT
42 Pnlbd Bkr,BAB 1 Pole 20A bkr
1 1 OOKA,SPD Standard+Surge Counter Features Package,with Circuit
Breaker
1 300KA,SPD Standard+Surge Counter Features Package,with Circuit
Breaker
1 6'Door
2 12'Door
E _T •N Detail Bill of Material , a
Project Name: CCUA Governors Park RWPS and Negotiation No: JW30927X2K2
FbweAgg 8usreress Woridivirla WW LS
General Order No: Alternate No: 0002
Qty List of Materials
1 18"Door
1 Thermostat-for enclosure space heater control
5 Structure Floor Leveling Channel Sills
5 Fire Wall Barters between each section
4 600A Vertical Bus(Tin-plated Cu)
1 Rodent Barriers both sides
1 2B Wiring
5 Bottom Vertical Bus Barrier
5 Labyrinth,Isolatedllnsulated vertical bus barrier with shutters
5 600A Hors.Cu Gnd Bus,1/4"x 2'Bar
5 85KA Bus Bracing
1 1200A Vertical Bus(Tin-plated cu)
5 Structure Bottom plates Included with NEMA 12
5 Tin Plated horizontal bus
5 1200A Copper Fmt Mtd 21'N12 Dust Tight
1 CONTROL RELAYS WHERE APPLICABLE TO BE EATON D3 TYPE,
EXCEPTION FOR'RR'IN WELL PUMP DUE TO CONTACT
REQUIREMENTS.
1 DIVERSIFIED SLD SERIES 3 PHASE VM IS TO BE MOUNTED IN
METERING UNIT
1 METER TO BE PXM 2280
Eaton Selling Policy 25-000 applies.
All orders must be released for manufacture within 90 days of date of order entry. If approval drawings are required,drawings must be returned
approved for release within 60 days of mailing. If drawings are not returned accordingly,andlor If shipment is delayed for any reason,the price of the
order will Increase by 1.0%per month or fraction thereof for the time the shipment Is delayed.
to
Seller shall not be responsible for any failure to perform,or delay In performance of,Its obligations resulting from the COVID-19 pandemic or any
future epidemic,and Buyer shall not be entitled to any damages resulting thereof.
•
MCC General Information
MCC General Information Ind.Light Type 6v Xfmr
Wiring Diagram Type Eaton Standard
MCC Quantity Structure Schedule
Standards UL845,NEMA,NEC There are 2 etructure(s).
Special Codes UL AI structures have a 800 A vertical bus.
Service Voltage(3 Phase) 480 Total width of al sections Is 40"
Frequency 60 Height of ail sections is 91"
System 3PH3W
Witness Testing No Unit Modifications
Entrance
Enclosure Specifications ServiceLabel
Total Structures 2
Type NEMA 1 Gasketed
Depth 21"Front Mt Only
Height 90"
Horizontal Wlreways 9"High,Top&Bottom
Vertical Wlreways 4"
Channel Sills Yes
Bottom Plates None
150 Watt Space Heaters No
Space Heater Thermostat 1
Master Terminal Blodc Location None
IBC/CBC Seismic Qualified No
ABS Certified No
Bus System Specifications
Main Bus Amps 1200
Main Bus Material Copper
Main Bus Bar Plating Tin
Insulated Horiz.Bus No
1000Afsq in.Cu Bus No
Vertical Bus Amps See Structure Schedule
Vertical Bus Material Tin Plated Copper
Vertical Bus Barrier Labyrinth,Isolated/
tO Insulated with shutters
Bus Bracing 65,000
Ground Bus 600
Ground Bus Location Top
Ground Bus Lug Size 1-#6-350Kcmil
Ground Bus Lug Type Screw
Plug-in 300AVert.Gnd.Bus No
Neutral None
Horizontal Bus Temperature Rise 65 deg C
Bottom Vert Bus Barrier Yes
Vertical Ground Bus No
Incoming Line Termination
Device:NGH-C Maln Bkr(1200A trip),Lugs:4-#1/0-750Kanll
Cable Entry Bottom
Splice Kit/Transition None
MCC Type Match Up
MCC Type Match Up GO# "None"
MCC Starter Specifications
Wiring Class 2B
Control Voltage 120
Control Voltage Src Ind CPT
Nameplate Size 1"X 2.5"
Nameplate Color Black/Willie Letters
Pilot Dev.Model E34
The information on this document Is PREPARED BY DATE
mated by Eaton Corporation.It is Daniel Griffin enan022 Eaton Fayetteville, NC
disclosed In confidence and It la only to
be used for the purpose In which It Is APPROVED 9Y DATE JOB NAME CCUA Governors Park RWPS and VAN L8
supplied. DESIGNATION MCC-MAIN
VERSION TYPE DRAWING TYPE
1.02.8 Freedom+MCC Customer Appr.
NEO 4JNumbx REVISION I DWG ME G.O. rrat smut
Ar/Sea 7K2K?aoo7 A 1 of 4
Notes/Special Instructions
CONTROL RELAYS WHERE APPLICABLE TO BE EATON D3 TYPE.
MCB ARMS Switch to be on front of door.
to
The Informadon on this document Is PREPARED BY DATE
created by Eaton Corporation.It is Daniel Griffin iner2o223 Eaton Fayetteville, NC
disclosed In confidence end It is only to
be used for the purpose In which It Is APPROVED BY DATE JOB NAME CCUA Governors Park RWPS and WW LS
supplied. DEBIDNAI1ON MCC-MAIN
VERSION TYPE 1 DRAIA NGTYPE
1.0,2.8 Freedom+MCC CustomerAppr.
NED-ALT Number REVISION DNG SIZE 0.0. REM SHEET
JV1110127x2R2-0002 A 2 of
Top View
5.41 5.41
2F 1F
A
B SPD
C
D
F
G
H
Sub Feed
K
to L
M NIGH-C312C
!�20.156*20.078>j
1.25 1.25
a
N ItD
I
ImliVENOMMLNI
20.156 20.078
Floor View
The Infamdlon on this document Is PREPARED BY DATE
created by Eaton Corporation.It Is Dulled Griffin s/2e12022 Eaton Fayetteville,NC
disclosed In confidence and It Is only to APPROVED BY D CCUA Governors Perk RWPS and WW LS
sbe upplied.
used for the purpose In which H IsDESIGNATION MCC•MAIN
supplied.
VERSION TYPE DRAINING TYPE
1.O.2.11 Freedoms MCC Customer Appr.
NEO-ALTNumber REVISION OWO SIZE 0.0. ITEM SHEET
✓vr1o1127x21C2-00o2 _ A _l , i Sof4
Unit Name In etc Description Class Starter Size $kr/Sw Slnit
HEIFER aka F etures
Wire D(ap, Trio/Clip
2M MAIN BREAKER NGH-C Main Bkr NGH-C 1 RMS 310+ALSIG Trip WI GF
(1200A trip),Lugs: SP 1 Main Bkr Shunt Trip
4-#1/0-750Kcm11 NONE 1200
1B SPD 3001(A,SPD Standard
+Surge Counter
Features Package,with NONE
Circuit Breaker
1D 12"Door
1 F 12"Door
1 H 12"Door _
1M MAIN LUGS #2-600 Kcmll 4/Ph
Sub Feed Lugs(Screw
(Screw) NONE
tO
The Information on thls document Is PREPARED BY DATE
created by Eaton Corporation.It Is Denial Griffin 2128/2022 Eaton Fayetteville,NC
disclosed In confidence and it Is only to -
be used for the purpose In which It le APPROVED BY DATE JOE NAME CCUA Governors Park RWPS and WW LE
supplied. DEMONATION MCC-MAIN
VERSION TYPE TYPE
1A.2.8 Freedom+MCC fDRAIMNG
CustomerAppr.
•
NEG-ALT Number REVISION DWG BIM O.O. ITEM SHEET
JVM0e27X2K2.9002 A 4 of 4
MCC General Information
MCC General Information Nameplate Color Black/White Letters
Wring Diagram Type Eaton Standard Pilot Dev.Model E34
MCC Quantity Ind.Light Type 6v Xfmr
Standards UL845,NEMA,NEC PL Color(On) Red
Spada!Codes UL PL Color(Off) Green
Service Voltage(3 Phase) 480 PL Color(O.L.Trip) Blue
Frequency 60
Systystem 3PH3W Structure Schedule
Witness Testing No There are 5 structtre(s).
Structure(s)1 have a 1200 A Vertical Bus.
Enclosure Speclflcatlons Structure(a)2,3,4,5 haves 800 A Vertical Bus.
Total Structures 5 Total width of all sections is 144"
Type NEMA 12 Dust tight Height of all sections Is 91"
Depth 21"Front Mt Only
Heigh 90" Unit Modifications
Horizontal WIrewaya 9"High,Top&Bottom I#14awg SIS Control Wire
Vertical Wreways 4" Terminal Block-Latching Pul-Apart,Std.
Channel Sills Yes Wtremarkers at Each End
Bottom Platen Standard Coll Surge Suppressor
150 Watt Space Heaters No SIS Power Wre
Space Heater Thermostat 1
Master Terminal Block Location None
IBC/CBC Seismic Qualified No
ABS Certified No
Bus System Specifications
Main Bus Amps 1200
Main Bus Material Copper
Main Bus Bar Plating Tin
Insulated Horiz.Bus No
1000A/sq in.Cu Bus No
Vertical Bus Amps See Structure Schedule
Vertical Bus Material Tin Plated Copper
Vertical Bus Barrier Labyrinth,Isolated/
Insulated with shutters
Bus Bracing 65,000
Ground Bus 600
Ground Bus Location Top
Ground Bus Lug Size 1-06-350Konil
Ground Bus Lug Type Screw
Plug-In 300AVert.Gnd.Bus No
Neutral None
Horizontal Bus Temperature Rise 65 deg C
Bottom Vert.Bus Barrier Yes
Vertical Ground Bus No
incoming Line Termination
<Text columnspan•"2">Device:*2-600
Kcmll 4/Ph Main Lugs(Screw)&CTa</
Text>
Cable Entry Bottom
Splice Kit/Transition None
MCC Type Match Up
MCC Type Match Up GOg "None"
MCC Starter Specifications
Wring Class 2B
Control Voltage 120
Control Voltage Src Ind CPT
Nameplate Size 1"X 2.5"
The Information on this document Is PREPARED BY DATE
cleated by Eaton Corporation.It Is Daniel SWIM e/28/2022 Eaton Fayetteville, NC
disclosed In confidence and It Is only to be used for the purpose In which It is APPROVED BY DATE .1OS NAME CCUAGovamors Parts RWPS and WW LS
supplied. DESIGNATION MCC-1
VERSION TYPE DRAWING TYPE
1.0.2.8 Freedom+MCC CustomerAppr.
NEO-ALTNumber REVISION DNOSIZE D.O. ITEM SHEET
Arra0127X21k2410022 A 1 of 5
Notes/Special Instructions
CONTROL RELAYS WHERE APPLICABLE TO BE EATON D3 TYPE. EXCEPTION FOR"RR"IN WELL PUMP
DUE TO CONTACT REQUIREMENTS.
DIVERSIFIED SLD SERIES 3 PHASE VM IS TO BE MOUNTED IN METERING UNIT
METER TO BE PXM 2280
The Information on this document Is 'PREPARED BY DATE
created by Eaton Corporation.It Is Daniel Griffin er28=22 Eaton Fayetteville,NC
disclosed In confidence and It Is only to
be used for the purpose to which It Is APPROVED BY DATE JOB NANE CCUA Gowmors Park RWPS and WW LS
supplied. 1 DESMINATION MCC-1
VERSION TYPE DRAWING TYPE
1.02.8 Freedom+MCC Customer Appr.
NEO•ALTNumber REVISION DWG SIM 0.0. Mil SHEET
.MSO227X2K2A002 ± A 2 of 5
Top View
i
5.41 5.41` 5.41 5.41y 5.41
57.5 ) ,�/.o 21. '17"g'a ��7'3
5F 4F 3F 2F 1F
A
42CKT «' '
B DG1 Drive DG1 Drive SPD
FR8 FR6
C 281AVT 281AVT •• .
D SPD
E i• II
F
MLO
G 1 IN la MTR
H i31
.1 HFD3020
K
to L
M 1 30KVA
40.155 40.078 24.078 20.078>20.078)
1.25 1.25 1.25 1.25 1.25
c.ict
1.25 1 1.25 1.25 1.25 1.25
ii -. ..(--- 1
40.156 40.078 24.078 20.078 20.078
Floor View
The Information on this document Is iPREPARSD BY DATE
created by Eaten Corporation.It Is Daniel GrifIM 9/28/2022 Eaton Fayetteville, NC
disclosed In confidence and it la only to — •
be used for the purpose In which It Is APPROVED BY DATE Joe NAME CCUA Governors Park RWPS and W1N LS
supplied. DESIGNATION MCC-1
VERSION TYPE DRAWING TYPE
1.02.8 Freedom+MCC CustomerAppr.
1.NEO•ALT Number REVISION DWG 5I 0.0. ITEM SHEET
mace xaxs.00ea 1 A 3 of 6
Unit Nameplate DelaUSW Class Starter Size &gag Unit
13P/FLA Pales Featur
W Diag. Tho/Cllp
5M RWPS DG1 VFD,Variable HMCP 1 Blank Device Panel
HSP NO.2 torque, 261 FLA, 200/261 3P 1 Speed Pot 1000 Ohm
480V,HMCP NONE 400 4 C-H Model D7,300V,3 Pole Socket
Relay
1 Pilot Ught-E34-LED(On,Run,
Fast,Forward)
1 Pilot Light-E34-LED(Off,Stopped)
1 Pilot Light-E34-LED(Overload
Trip)
1 Panel Elapsed lime Meter
(Standard)
1 3 Pos.Sal.Sw.,E34(Hand-Off-
Auto)
1 DG1 Dv/Dt Output Filter-FR6
1 3 x DI,3 x DO, 1 x thermistor,24
Vdc/EXT option card
1 1 x Al,2 x AO(Isolation to control
board of on card
4M RWPS DG1 VFD,Variable HMCP 1 Blank Device Panel
HSP NO.1 torque, 281 FLA, 200/261 3P 1 Speed Pot 1000 Ohm
480V, HMCP NONE 400 4 C-H Model D7,300V,3 Pole Socket
Relay
1 Pilot Ught-E34-LED(On,Run,
Fast,Forward)
1 Pilot Light-E34-LED(Off,Stopped)
1 Pilot Light-E34-LED(Overload
Trip)
1 Panel Elapsed Time Meter
(Standard)
1 3 Pos.Sal.Sw.,E34(Hand-Off-
Auto)
1 DG1 Dv/Dt Output Filter-FR6
1 3 x DI,3 x DO,1 x thermistor,24
Vdc./EXT option card
tO 1 1 xAi,2 x AO(Isolation to control
board,o:,r,on card
3F PANEL L1 PL1A Panelboard 42 Pnlbd Bkr,BAB 1 Pole 20A bkr
226A 120/208V 3PH
4W 42 CKT 5A10398.DWF
3M T-L1 30 Kva 3 ph,440-480
/120-208V High
Efficiency Xfmr,50A Pri., 5A10398.DWF
110A Sec.Bkr.
2B PANELBOARD 100KA,SPD Standard
+Surge Counter
Features Package,with NONE
Circuit Breaker
2D 300KA,SPD Standard
+Surge Counter
Features Package,with NONE
Circuit Breaker
2G PXM2270
NONE
2J HYPO ROOM HFD Bkr(20A trip) HFD
UNIT HEATER 3P
5599A85.DWF 20
2L 1:"Door
2M 6"Door
1B 12"Door
1 E 18"Door
The Information on this document Is PREPARED BY DATE
created by Eaton Corporation.It Is Daniel artm 9l28/2022 Eaton Fayetteville, NC
disclosed In confidence and It h only to --be used for the purpose In which It is APPROVED BY DATE JOB NAME CCUAGovsmors Perk RUMPS and WN LS
supplied. DESIGNATION MCC-1
--- VERSION TYPE DRAWING TYPE
1.0.2.8 Freedom+MCC Customer Appr.
NEG-ALT Number REVISION DWG am MO. ITEM - SHEET
JVreoe27x2x2-0002 A 4 of6
f
Unit Nameplate Deastiptlen ram Starter Slz@ BkrlSw !lnIt
HP_/ELA Piles Features
Wire Ding, Trin/Clo
1 M #2-800 Kcmll 4/Ph
Main Lugs(Screw)&
CTs NONE
tO
The Information on this document Is PREPARED BY DATE
created by Eaton Corporation.It Is Daniel o,rnn el2e/2o221 Eaton Fayetteville, NC
disclosed In contldence and It Is only to —
be used fortha purpose In which It la APPROVED BY DATE JOB NALIE CCUAGovsrnors Park RWPS and VAN ILS
supplied. DEerONATION MCC-1
VERSION TYPE DRAWNG TYPE
1.0.2.8 Freedom+MCC CustomerAppr.
NEG-ALTNumber REVISION DWG SIZE O.O. RBI MIT
Jv73oa27x2K-0002 , A 5015
Brooks
Building Solutions
PROPOSAL
Clay County Utility Authority September 29,2022
Project-Peter's Creek WWTP
3176 Old Jennings Road
Middleburg, Florida 322068
Attention: Paul Stelnbrecher
We propose to furnish the following equipment and services for the above referenced project.
Brooks Building Solutions standard TERMS AND CONDITIONS apply to this proposal and price
quotation,with the EXCEPTION for this Project Only: Terms of Payment, Net 5 days, Mark up for
Equipment reduced from 25%to 10%.
This Proposal includes:
Providing Eaton Engineering Services/Equipment/Submittals for the Peter's Creek WWTP Rev.C Expansion
Project.
• Provide Submittals/Drawings from Eaton Manufacturing.
• Provide Factory Start Up for Eaton MCC-1 —7, MCC MAIN-1 and MCC MAIN-2, Equipment as shown
in the bill of material, see attached.
to • Provide Eaton Motor Control Centers, MCC-1 —7, MCC MAIN-1 and MCC MAIN-2, as per bill of
material, see attached.
• Provide Eaton Manufacturing 3-year Warranty, see attached.
• All orders must be released for manufacture within 90 days of date of order, If approval drawings are
required,drawings must be returned approved for release within 60 days of mailing. If drawings are not
returned accordingly, and/or if shipment is delayed for any reason,the price of the order will increase
by 1.0% per month or fraction thereof for the time the shipment is delayed.
• Seller shall not be responsible for any failure to perform, or delay in performance of, its obligations
resulting from the COVID-19 pandemic or any future epidemic, and Buyer shall not be entitled to any
damages resulting thereof.
Exclusions and Conditions of This Proposal:
• Brooks Building Solutions, Inc. will not be held responsible for any damaged equipment,equipment lost
after it has been received.
• Brooks Building Solutions, Inc. will not be responsible for any changes or delays for this Equipment
purchased. Lead Time are projected dates and cannot be Guaranteed.
• Any Price Increase from the Manufacture will Result in a Change Order for Price Increase.
• Any additional Equipment needed will be purchase with an Approved Change Order approved by
CCUA.
• Components or labor for items deemed necessary but are not included in the original scope of work will
be considered an extra cost to project and will only be performed with the expressed authorization of
the customer and invoiced to the customer at the non-contract customer labor rate.
Pape Jul]
Corporate 14301 Beverly Avenue I Jacksonville,FL 32210 I P 904.642.5303 I F 904.641.8722
Tellahaascc I2815-1 Industrial Plaza Dr.I Tallahassee.FL 32301 I P B50.701.2350I F 850.7012355
11,CA C0..4729 IIVAC 143UII'aIFA11'I RUr1J11N'U AU1t,b1A'ra1N 11.1.11,AUY SOCU'I1ONS 1MIMIC!: I PAR Ili UA:CN 21/16e(
2111 VU6.e1
• This proposal Is only valid for thirty(30)days from the date of issue.
• Full freight is allowed,and all applicable taxes are Included.
Proposed Price:
Nine Hundred Thirty-Nine Thousand Three Hundred Eighty-Seven and 00/100 Dollars-$939,387.00
TERMS AND CONDITIONS
This ement is sut' ct to the TERMS AND CONDITIONS included in this Proposal
Bro ks Building Sollutions,In Clay County Utility Authority
47../0
Jeff Hendricks
Senior Project Manager
Date: September 29,2022 Date:
to
Pap 2 an
Corporate 14501 Beverly Avenue 1 Jacksonvlllc,FL 322101 P 904.642.3303 1 F 904.641.8722
Tallahassee 12815-I induct-la]Plaza Dr.1 Tallahaaacc.FL 32301 1 P 850.701.23501 F 850.701.2353
Fl.;CA C'INN77u IIYAC IANIPMLNT I nuIr.IMNU AUTOMATION IIetFJWY NCII UIll1NN I a IAVK.'N I I'AK'IN UA:CN JMIuou
2111a,os.ol
E ,T•N Detail Bill of Material o I of I I
Project Name: CCUA Peters Creek WWTP Negotiation No: JV730705X2K1
y ing Busmen General Order No: Alternate No: 0003
Item No. Qty Product Description
1 EESS Services EESS Short Circuit and Coordination Studies:Arc Flash Hazard
Analysis,PE Review!Stamp Required-Florida
"'h&c)Approval Drawings for Clarifications and Exceptions'
Daniel Griffin
Designation Study
Qty Lilt of Materials
1 ESS Study-BidManager
1 2 Weeks Lead lime for Data Request Submittal
1 6-8 Weeks Lead Time for Study Completion
1 Quoted by Bid Manager
1 PE Review Stamp Required(Florida)
1 Arc Flash study
Item No. Qty Product Description
1 Engineering Services EESS Start-up
EESS Start-up
Designation EESS Start-up
to Item No. Qty Product Description
1 Motor Control Centers 60 Hz,Class 2B Wring,480V 3-Phase Service,65,000 Bracing,
Short Circuit Rating,Bottom Incoming, NEMA 1 Gasketed 21'
Front Mt Only enclosure,800A Copper Main Horizontal Bus,No
Neutral,Main Breaker.Used X-Space:20,Blank X-Space:4,
Future X-Space:0,MCC Lead Time Code:B.
Designation MCC-MAIN-1
Qty List of Materials
1 NGH-C Main Bkr(800A trip),Lugs:4-#4/0-500Kcmi1
1 Service Entrance Label
1 RMS 310+ALSIG Trip wl GF
1 Main Bkr Shunt Trip
1 Warm Contact Circuit Breaker Sw.
1 Main Bkr Auxiliary Interlock 1 NO-1 NC
1 300KA,SPD Standard+Surge Counter Features Package,with Circuit
Breaker
2 12'Door
1 Thermostat-for enclosure space heater control
2 Handlemech extension for top units
2 Structure Floor Leveling Channel Site
2 Fire Wall Barriers between each section
2 600A Vertical Bus(Tin-plated cu)
1 Rodent Barriers both sides
1 2B Wiring
2 Bottom Vertical Bus Barrier
2 Labyrinth,isolated/insulated vertical bus barrier with shutters
2 300A Horiz.Cu Gnd Bus,1/4"x 1"Bar
2 65KA Bus Bracing
2 Tin Plated horizontal bus
EE.:T•N Detail Bill of Material P e of
Project Name: CCUA Peters Creek WWTP Negotiation No: JV730705X2K1
powercrp t sirrass 144r drfe General Order No: Alternate No: 0003
Qty List of Materials
2 800A Copper Fmt Mtd 21'NEMA 1 Gasketed
1 #1/0-750 Kcmil 4/Ph Sub Feed Lugs(Screw)
Item No. Qty Product Description
1 Motor Control Centers 60 Hz,Class 2B wiring,480V 3-Phase Service,65,000 Bracing,
Short Circuit Rating,Bottom Incoming,NEMA 1 Gasketed 21'
Front Mt Only enclosure,2000A Copper Main Horizontal Bus,No
Neutral,Main Breaker.Used X-Space:26,Blank X-Space:10,
Future X-Space:0,MCC Lead Time Code:B.
Designation MCC-MAIN-2
Qty List of Materials
1 RGH-C Main Bkr(2000A trip),Lugs:6-#2-600Kcmil
1 Service Entrance Label
1 RMS 310+ALSlG Trip w/GF
1 Main Bkr Shunt Trip
1 Alarm Contact Circuit Breaker Sw.
1 Main Bkr Auxiliary Interlock 1 NO-1 NC
1 300KA,SPD Standard+Surge Counter Features Package,with Circuit
Breaker
5 17 Door
1 Thermostat-for enclosure space heater control
2 Handlemech extension for top units
3 Tin Plated horizontal bus
3 Fire Well Bafflers between each section
3 600A Vertical Bus(Tin-plated cu)
to 1 2B Wiring
3 Bottom Vertical Bus Barrier
3 Labyrinth,Isolated/Insulated vertical bus barrier with shutters
3 65KA Bus Bracing
3 600A Horiz.Cu Gnd Bus, 1/4"x 2'Bar
3 2000A Copper Frnt Mtd 21'NEMA 1 Gasketed
1 #1/0-750 Kcmil 6/Ph Sub Feed Lugs(Screw)
Item No. Qty Product Description
1 Motor Control Centers 60 Hz,Class 2B wiring,480V 3-Phase Service,65,000 Bracing,
Short Circuit Rating,Bottom Incoming,NEMA 12 Dust tight 21'
Front Mt Only enclosure,800A Copper Main Horizontal Bus,No
Neutral.Used X-Space:49,Blank X-Space: 11,Future X-Space:
0,MCC Lead Time Code:U.
Designation MCC-1
Qty List of Materials
1 PXM2270 METER/DISPLAY 60HZ 5A 90-265V AC/DC
1 PXM2270
2 600V Potential transformer
3 800A Current transformer
1 FVC Contactor Size 3[TM Ckt Brit]
1 LGH Bkr(600A trip)
2 HFDTwin Bkr(100A/100A trip)
1 HFDTwin Bkr(50A/100A trip)
1 150VA Individual CPT,Fused
1 N.C.Starter Aux Contacts,Size 1-4
ElT•N Detail Bill of Material E of
Project Name: CCUA Peters Creek WWTP Negotiation No: JV730705X2K1
toweliv Beakless vityldw>tde General Order No: Alternate No: 0003
Qty List of Materials
1 N.O.Starter Aux Contacts,Size 1-4
1 #16awg,MTW Control Wire
1 Coil Surge Suppressor
1 ATC-900 controller
1 Terminal Block-Latching Pull-Apart,Std.
1 Wiremarkers at Each End
1 Pilot Light-10250T-LED(On)
1 Pilot Light-10250T-LED(Off)
1 3 Pos.Sel.Sw.,10250T(Hand-Off-Auto)
1 34c.Logic Extender Cable 96'
1 Motor Load Block(100A)
1 45 Kva 3 ph,440-480V 1120-208V High Efficiency Xfmr,70A Pri.,175A
Sec.Bkr.
1 PL1A Panelboard 225A 1201208V 3PH 4W 42 CKT
1 PL1A Panalboard 100A 1201208V 3PH 4W 18 CKT
78 Pnlbd Bkr,BAB 1 Pole 20A bkr
1 Eaton Automatic Transfer Sw.,ATV9,800A,3P,ATC-900 controller
1 14d.Aux Relay Contacts Emergency Source Available(4 Form C)
1 14c.Aux Relay Contacts Normal Source Available(4 Form C)
1 300KA,SPD Standard+Surge Counter Features Package,with Circuit
Breaker
1 100KA,SPD Standard+Surge Counter Features Package,with Circuit
Breaker
1 6"Door
5 12'Door
1 Thermostat-for enclosure space heater control
3 Handlemech extension for top units
5 600A Vertical Bus(Tin-plated Cu)
5 Structure Bottom plates Included with NEMA 12
to 5 Structure Floor Leveling Channel Sills
5 Fire Wall Barriers between each section
1 Rodent Barriers both sides
1 2B Wiring
5 Bottom Vertical Bus Barrier
5 Labyrinth,Isolated/Insulated vertical bus barrier with shutters
5 300A Horiz.Cu Gnd Bus, 114'x 1'Bar
5 65KA Bus Bracing
5 Tin Plated horizontal bus
5 800A Copper Frnt Mtd 21'N12 Dust Tight
1 PROVIDE EATON D65 3 PHASE VM IN METERING UNIT WITH OUTPUT
CONTACTS RUN TO TB.
1 5B TO BE WIRED TO 42 CKT PANELBOARD.SHALL BE 208V 3 PH
RATED
i WIRE 5E CONTACTOR LINE SIDE FROM 3 POLE BREAKER IN L1.
WIRE LOAD OF CONTACTOR TO MLO IN PANEL L1 SECTION 2.
1 METER TO BE PXM2280
Item No. QV Product Description
1 Motor Control Centers 60 Hz,Class 2B wiring,480V 3-Phase Service,65,000 Bracing,
Short Circuit Rating,Bottom Incoming, NEMA 12 Dust tight 21'
Front Mt Only enclosure,2000A Copper Main Horizontal Bus,No
Neutral,Mein Lugs.Used X-Space:70,Blank XSpace: 14,Future
X-Space:0,MCC Lead Time Code: U.
Designation MCC-2
E s N Detail Bill of Material o
Project Name: CCUA Peters Creek WWTP Negotiation No: JV730705X2K1
powering Business,wor iwrafa General Order No: Alternate No: 0003
Qty List of Materials
1 PXM2270 METER/DISPLAY 60HZ 5A 90-265V AC/DC
1 #1/0-750 Kcmil 6&Ph Main Lugs(Screw)&CTs
1 PXM2270
2 600V Potential transformer
3 2000A Current transformer
1 FVC Contactor Size 3[TM Ckt Brit]
3 HFD Bkr(100A trip)
3 HFD Bkr(50A trip)
4 HMDL Bkr(600A trip)
1 150VA Individual CPT,Fused
1 N.C.Starter Aux Contacts,Size 1-4
1 N.O.Starter Aux Contacts,Size 1-4
1 3 Pos.Sel.Sw., 10250T(Hand-Off-Auto)
1 Pilot Light-10250T-LED(On)
1 #16awg,MTW Control Wire
1 Terminal Block-Latching Pull-Apart,Std.
1 Wiremarkers at Each End
1 Coil Surge Suppressor
1 Pilot Light-10250T-LED(Off)
7 Motor Load Block(100A)
1 45 Kva 3 ph,440-480V/120-208V High Efficiency Xfmr,70A Pri., 175A
Sec.Bkr.
1 PL1A Panelboard 100A 120/208V 3PH 4W 18 CKT
1 PL1A Panelboard 225A 120/208V 3PH 4W 42 CKT
102 Pntbd Bkr,BAB 1 Pole 20A bkr
1 300KA,SPD Standard+Surge Counter Features Package,with Circuit
Breaker
1 100KA,SPD Standard+Surge Counter Features Package,with Circuit
Breaker
to 2 12'Door
3 18'Door
1 6'Door
1 Thermostat-for enclosure space heater control
7 600A Horiz.Cu Gnd Bus, 1/4"x 2'Bar
1 800A Vertical Bus(Tin-plated cu)
2 Handlemech extension for top units
7 Structure Bottom plates Included with NEMA 12
7 Structure Floor Leveling Channel Sills
7 Fire Wall Barriers between each section
1 Rodent Barriers both sides
1 2B Wiring
7 Bottom Vertical Bus Barrier
7 Labyrinth,Isolated Insulated vertical bus barrier with shutters
7 65KA Bus Bracing
5 600A Vertical Bus(Tin-plated cu)
7 Tin Plated horizontal bus
7 2000A Copper Fmt Mtd 21'N12 Dust Tight
1 PROVIDE EATON D65 3 PHASE VM IN METERING UNIT WITH OUTPUT
CONTACTS RUN TO TB.
1 7B TO BE WIRED TO 42 CKT PANELBOARD.SHALL BE 208V 3 PH
RATED
1 WIRE 7E CONTACTOR LINE SIDE FROM 3 POLE BREAKER IN L1.
WIRE LOAD OF CONTACTOR TO MLO IN PANEL L1 SECTION 2,
1 METER TO BE PXM2280
Detail Bill of Material acE
IF.AT•RII Project Name: CCUA Peters Creek WWTP Negotiation No: JV730705X2K1
powenagBusinesswniidwide General Order No: Alternate No: 0003
Item No. Qty Product Description
1 Motor Control Centers 60 Hz,Class 2B wiring,480V 3-Phase Service,65,000 Bracing,
Short Circuit Rating,Bottom Incoming,NEMA 12 Dust light 21'
Front Mt Only enclosure,600A Copper Main Horizontal Bus,No
Neutral,Main Lugs.Used X-Space:31,Blank X-Space:5,Future
X-Space:0,MCC Lead Time Code:U.
Designation MCC-7
Qty Ust of Meterlals
1 #4-350 Kcmil 4/Ph Main Lugs(Screw)
1 FVC Contactor Size 3[TM Ckt Mc]
1 HFD Bkr(100A trip)
1 150VA Individual CPT, Fused
1 N.C.Starter Aux Contacts,Size 1-4
1 N.O.Starter Aux Contacts,Size 1-4
2 Motor Load Block(100A)
1 Pilot Light-10250T-LED(On)
1 Pilot Light-10250T-LED(Off)
1 Terminal Block-Latching Pull-Apart,Std.
1 #16awg,MTW Control Wire
1 Coil Surge Suppressor
1 Wiremarkers at Each End
1 3 Pos.Sel.Sw., 10250T(Hand-Off-Auto)
1 30 Kva 3 ph,440-480V/120-208V High Efficiency Xfmr,50A Pri.,110A
Sec.Bkr.
1 PL1A Panelboard 100A 120/208V 3PH 4W 18 CKT
1 PL1A Panelboard 225A 120/208V 3PH 4W 42 CKT
78 Pnlbd Bkr,BAB 1 Pole 20A bkr
to 1 100KA,SPD Standard+Surge Counter Features Package,with Circuit
Breaker
1 6'Door
2 12'Door
1 Thermostat-for enclosure space heater control
3 Structure Bottom plates Included with NEMA 12
3 Tin Plated horizontal bus
3 Fire Wall Barriers between each section
3 600A Vertical Bus(Tin-plated cu)
1 Hendlemech extension for top units
1 Rodent Barriers both sides
1 2B Wiring
3 Bottom Vertical Bus Barrier
3 Labyrinth,Isolated/insulated vertical bus barrier with shutters
3 65KA Bus Bracing
3 Structure Floor Leveling Channel Sills
3 300A Hor¢.Cu Gnd Bus, 1/4"x 1'Bar
3 600A Copper Fmt Mtd 21'N 12 Dust Tight
1 #4-350 Kcmil 4/Ph Sub Feed Lugs(Screw)
1 3F TO BE WIRED TO 42 CKT PANELBOARD.SHALL BE 208V 3 PH
RATED
1 WIRE 2D CONTACTOR LINE SIDE FROM 3 POLE BREAKER IN L2.
WIRE LOAD OF CONTACTOR TO MLO IN PANEL L3 SECTION 2.
E LT•N Detail Bill of Material
Project Name: CCUA Peters Creek WWTP Negotiation No: JV730705X2K1
powering Jos weddleide General Order No: Alternate No: 0003
item No. Qty Product Description
1 Motor Control Centers 60 Hz,Class 2B wiring,480V 3-Phase Service,65,000 Bracing,
Short Circuit Rating,Bottom Incoming,NEMA 12 Dust tight 21'
Front Mt Only enclosure,600A Copper Main Horizontal Bus,No
Neutral,Main Lugs.Used XSpace:59,Blank X-Space:25,Future
X-Space:0,MCC Lead Time Code:U.
Designation MCC-3
Qty List of Materials
1 PXM2270 METER/DISPLAY 60HZ 5A 90-265V AC/DC
1 #2-600 Kcmil 2/Ph Main Lugs(Screw)&CTs
1 PXM2270
2 600V Potential transformer
3 600A Current transformer
3 FVNR Starter Size 1 [HMCP]
1 FVNR Starter Size 2[HMCP]
3 DG1 VFD,Constant torque,23 FLA,480V,HMCP
1 DG1 VFD,Constant torque,205 FLA,480V,HMCP
1 HFD Bkr(40A trip)
1 HFD Bkr(20A trip)
4 150VA Individual CPT,Fused
4 N.O.Starter Aux Contacts,Size 1-4
4 N.C.Starter Aux Contacts,Size 1-4
3 DG1 Dv/Dt Output Fitter-FR2
5 Pilot Ligh1-10250T-LED(Misc)
4 Heater Packs Supplied
8 Coil Surge Suppressor
8 Wiremarkers at Each End
to 8 Terminal Block-Latching Pull-Apart,Std.
4 Bi-Metalic Overload Relay(Standard)c/w Heater Packs
8 #16awg,MTW Control Wire
4 Pilot Light-10250T-LED(Stopped)
4 Pilot Light-10250T-LED(Run)
1 DG1 Dv/Dt Output Fitter-FR6
1 1 Unit PB, 10250T(Reset)
2 C-H Model TRN Solid State On-Delay Timer
1 C-H Model AR Machine Tool Relay,600V,6 Pole
1 2 Unit PB,10250T(Start/Stop)
4 Speed Pot 1000 Ohm
9 Motor Load Block(100A)
4 Pilot Light-10250T-LED(Off,Stopped)
7 3 Pos.Sel.Sw.,10250T(Hand-Off-Auto)
6 C-H Model D7,300V,3 Pole Socket Relay
4 Blank Device Panel
4 Pilot Light-10250T-LED(On,Run,Fast,Forward)
16 C-H Model 07,300V,4 Pole Socket Relay
4 Pilot Light-10250T-LED(Overload Trip)
1 300KA,SPD Standard+Surge Counter Features Package,with Circuit
Breaker
2 6"Door
1 18"Door
10 12'Door
1 Thermostat-for enclosure space heater control
7 Structure Bottom plates Included with NEMA 12
7 Structure Floor Leveling Channel Sills
7 Fire Wall Barriers between each section
7 600A Vertical Bus(Tin-plated cu)
1 Rodent Barriers both sides
1 2B Wiring
7 Bottom Vertical Bus Barrier
iFT Detail Bill of Material G t. f 41
. Project Name: CCUA Peters Creek WWTP Negotiation No: JV730705X2K1
powering&aims waithvide General Order No: Alternate No: 0003
Qty List of Materiab
7 Labyrinth,Isolated/Insulated vertical bus barrier with shutters
7 300A Hartz.Cu Gnd Bus,1/4"x 1'Bar
7 65KA Bus Bracing
2 Handlemech extension for top units
7 Tin Plated horizontal bus
7 600A Copper Fmt Mtd 21'N12 Dust Tight
1 METER TO BE PXM2280
1 AR RELAY IN CLARIFIER TO BE LATCHING RELAY
1 PROVIDE EATON D65 3 PHASE VM IN METERING UNIT WITH OUTPUT
CONTACTS RUN TO TB.
Item No. Qty Product Description
1 Motor Control Centers 60 Hz,Class 2B wiring,480V 3-Phase Service,65,000 Bracing,
Short Circuit Rating,Bottom Incoming,NEMA 12 Dust light 21'
Front Mt Only enclosure,600A Copper Main Horizontal Bus,No
Neutral,Main Lugs.Used X-Space:54,Blank X-Space:18,Future
X-Space:0,MCC Lead Time Code:U.
Designation MCC-4
Qty List of Materials
1 PXM2270 METER/DISPLAY 80HZ 5A 90-265V AC/DC
1 #2-600 Kcmil 2/Ph Main Lugs(Screw)&CTs
1 PXM2270
2 800V Potential transformer
3 600A Current transformer
3 FVNR Starter Size 1[HMCP]
to 1 FVNR Starter Size 2[HMCP]
1 DG1 VFD,Constant torque,205 FLA,480V,HMCP
2 DG1 VFD,Constant torque,23 FLA,480V,HMCP
3 HFD Bkr(50A trip)
4 150VA Individual CPT,Fused
4 N.O.Starter Aux Contacts,Size 1-4
4 N.C.Starter Aux Contacts,Size 1-4
4 BI-Metalic Overload Relay(Standard)clw Heater Packs
7 Terminal Block-Latching Pull-Apart,Std.
7 Wiremarkers at Each End
3 Speed Pot 1000 Ohm
7 Coil Surge Suppressor
3 Pilot Light-10250T-LED(Off,Slopped)
3 Blank Device Panel
4 Heater Packs Supplied
6 C-H Model D7,300V,3 Pole Socket Relay
3 Pilot Ught-10250T-LED(On,Run, Fast,Forward)
13 C-H Model D7,300V,4 Pole Socket Relay
3 Pilot Light-10250T-LED(Overload Trip)
7 #16awg,MTW Control Wire
2 C-H Model TRN Solid State On-Delay Timer
2 DG1 Dv/Dt Output Filter-FR2
5 Pilot Light-10250T-LED(Mist)
6 3 Pos.Sel.Sw.,10250T(Hand-Off-Auto)
1 1 Unit PB,10250T(Reset)
4 Pilot Light-10250T-LED(Run)
1 DG1 Dv/Dt Output Filter-FR6
1 C-H Model AR Machine Tool Relay,600V,6 Pole
1 2 Unit PB,10250T(Siert/Stop)
E L N Detail Bill of Material
Project Name: CCUA Peters Creek WWTP Negotiation No: JV730705X2K1
F'e►v rirl,g 13asr1 w ridNrotle General Order No: Alternate No: 0003
Qty Ust of Materials
9 Mote Load Block(100A)
4 Pilot Light-10250T-LED(Stopped)
1 300KA,SPD Standard+Surge Counter Features Package,with Circuit
Breaker
7 12"Door
4 6"Door
1 Thermostat-for enclosure space heater control
6 65KA Bus Bracing
6 300A Horiz Cu Gnd Bus,1/4'x 1'Bar
6 Labyrinth,Isolated/Insulated vertical bus barrier with shutters
6 Bottom Vertical Bus Barrier
1 2B Wiring
6 Fire Well Bafflers between each section
6 600A Vertical Bus(Tin-plated Cu)
6 Structure Floor Leveling Channel Sills
6 Structure Bottom plates Included with NEMA 12
2 Handlemech extension for top units
1 Rodent Barriers both sides
6 Tin Plated horizontal bus
6 600A Copper Fmt Mtd 21"N12 Dust Tight
1 METER TO BE PXM2280
1 AR RELAY IN CLARIFIER TO BE LATCHING RELAY
1 PROVIDE EATON D65 3 PHASE VM IN METERING UNIT WITH OUTPUT
CONTACTS RUN TO TB.
Item No. Qty Product Description
1 Motor Control Centers 60 Hz,Class 2B wiring,480V 3-Phase Service,65,000 Bracing,
to Short Circuit Rating,Bottom Incoming,NEMA 1 Gasketed 21"
Front Mt Only enclosure,800A Copper Main Horizontal Bus,No
Neutral,Main Breaker.Used X-Space:86,Blank X-Space:10,
Future X-Space:0,MCC Lead Time Code:U.
Designation MCC-5
Qty List of Materials
1 PXM2270 METER/DISPLAY 60HZ 5A 90-265V AC/DC
1 NGH-C Main Bkr(800A trip),Lugs:4-#4/0-500Kcmil
1 PXM2270
3 800A Current transformer
2 600V Potential transformer
1 FVNR Starter Size 2[HMCP]
4 DG1 VFD,Constant torque,140 FLA,480V,HMCP
1 DG1 VFD,Constant torque,72 FLA,480V,HMCP
2 HFD Bkr(50A trip)
1 HJD Bkr(250A trip)
1 150VA Individual CPT,Fused
1 N.C.Starter Aux Contacts,Size 1-4
1 N.O.Starter Aux Contacts,Size 1-4
6 #16awg,MTW Control Wire
6 Terminal Block-Latching Pull-Apart,Std.
6 Pilot Light-10250T-LED(Overload Trip)
1 Pilot Ught-10250T-LED(Run)
1 C-H Model D7,300V,2 Pole Socket Relay
6 3 Pos.Sel.Sw., 10250T(Hand-Off-Auto)
6 Wiremarkers at Each End
EIT•N Detail Bill of Material ! �.Project Name: CCUA Patera Croak WWTP Negotiation No: JV730705X2K1
BrlaSSwofkfiviits General Order No: Alternate No: 0003
Qty List of Materiels
1 Bi-Metalic Overload Relay(Standard)clw Healer Packs
8 Motor Load Block(100A)
1 Pilot Ught-10250T-LED(Stopped)
6 Coil Surge Suppressor
1 Alarm Contact Circuit Breaker Sw.
1 Main Bkr Auxiliary Interlock 1 NO-1 NC
1 RMS 310+LSI Trip
5 Blank Device Panel
1 DG1 DvlDt Output Filler-FR4
15 C-H Model D7,300V,4 Pole Socket Relay
5 Pilot Light-10250T-LED(On,Run,Fast,Forward)
5 Pilot Light-10250T-LED(Off,Stopped)
5 Speed Pot 1000 Ohm
4 DG 1 Dv/Ot Output Filter-FR5
1 Fdr Bkr Key Interim*
1 Heater Packs Supplied
1 300KA,SPD Standard+Surge Counter Features Package,with Circuit
Breaker
1 6'Door
3 12'Door
1 18"Door
1 Thermostat-for enclosure space heater control
8 Handlemech extension for top units
8 Structure Floor Leveling Channel Sills
8 Fire Well Banters between each section
8 600A Vertical Bus(Tin-plated cu)
1 Rodent Barriers both sides
1 2B Wiring
Bottom Vertical Bus Barrier
to Labyrinth,Isolated/Insulated vertical bus barrier with shutters
300A Horiz.Cu Gnd Bus, 1/4'x 1'Bar
65KA Bus Bracing
Tin Plated horizontal bus
800A Copper Frnt Mtd 21'NEMA 1 Gasketed
1 METER TO BE PXM2280
1 PROVIDE EATON D85 3 PHASE VM IN METERING UNIT WITH OUTPUT
CONTACTS RUN TO TB.
1 COORDINATE KIRK KEY WITH MCC-6
Item No. Qty Product Description
1 Motor Control Centers 60 Hz,Class 2B wiring,480V 3-Phase Service,65,000 Bracing,
Shod Circuit Rating,Bottom Incoming,NEMA 1 Gasketed 21'
Front Mt Only enclosure,800A Copper Main Horizontal Bus,No
Neutral,Main Breaker.Used X-Space:76,Blank X-Space:8,
Future X-Space:0,MCC Lead Time Code:U.
Designation MCC-6
Qty List of Materials
1 PXM2270 METER/DISPLAY 60HZ 5A 90-265V AC/DC
1 NGH-C Main Bkr(800A trip),Lugs:4-#410-500Kcmil
1 PXM2270
2 600V Potential transformer
3 800A Current transformer
Detail Bill of Material
E.AT•N Project Name: CCUA Peters Creek WWTP Negotiation No: JV730705X2K1
Paiverii9 B•rtess WorAdwoda General Order No: Alternate No: 0003
City List of Materials
1 FVNR Starter Size 2[HMCP]
3 DG1 VFD,Constant torque, 140 FLA 480V,HMCP
1 DG1 VFD,Constant torque,72 FLA,480V,HMCP
2 HFD Bkr(50A trip)
1 HJD Bkr(250A trip)
1 HFD Bkr(100A trip)
1 150VA Individual CPT,Fused
1 N.C.Starter Aux Contacts,Size 1-4
1 N.O.Starter Aux Contacts,Size 1-4
12 C-H Model D7,300V,4 Pole Socket Relay
5 Coil Surge Suppressor
5 Wiremarkers at Each End
5 Terminal Block-Latching Pull-Apart,Std.
1 BI-Metalic Overload Relay(Standard)c/w Heater Packs
5 #16awg,MTW Control Wire
8 Motor Load Block(100A)
5 Pilot Light-10250T-LED(Overload Trip)
1 Pilot Light-10250T-LED(Run)
1 C-H Model D7,300V,2 Pole Socket Relay
5 3 Pos.Sel.Sw.,10250T(Hand-Off-Auto)
1 Fdr Bkr Key Interlock
1 Heater Packs Supplied
3 DG1 Dv/Dt Output Flier-FR5
4 Speed Pot 1000 Ohm
1 RMS 310+LSI Trip
1 Alarm Contact Circuit Breaker Sw.
1 Main Bkr Auxiliary Interlock 1 NO-1 NC
4 Pilot Light-10250T-LED(Off,Stopped)
4 Blank Device Panel
to 1 DG1 Dv/Dt Output Filter-FR4
4 Pilot Ligh1-10250T-LED(On,Run,Fast,Forward)
1 Pilot Light-10250T-LED(Stopped)
1 300KA,SPD Standard+Surge Counter Features Package,with Circuit
Breaker
1 6'Door
2 12'Door
1 18'Door
1 Thermostat-for enclosure space heater control
7 Handlemech extension for top units
7 Structure Floor Leveling Channel Sills
7 Fire Wall Barriers between each section
7 600A Vertical Bus(Tin-plated a)
1 Rodent Barriers both sides
1 2B Wiring
7 Bottom Vertical Bus Barrier
7 Labyrinth,Isolated/Insulated vertical bus barrier with shutters
7 300A Horiz.Cu Gnd Bus,1/4"x 1'Bar
7 65KA Bus Bracing
7 Tin Plated horizontal bus
7 800A Copper Fmt Mtd 21'NEMA 1 Gasketed
1 METER TO BE PXM2280
1 PROVIDE EATON D65 3 PHASE VM IN METERING UNIT WITH OUTPUT
CONTACTS RUN TO TB.
1 COORDINATE KIRK KEY WITH MCC-5
Eaton Selling Policy 25-000 applies.
E.AT•N Detail Bill of Material a
Project Name: CCUA Peters Creek WWTP Negotiation No: JV730705X2K1
powering&sirrassWorkhkra General Order No: Alternate No: 0003
All orders must be released for manufacture within 90 days of date of order entry. If approval drawings are required,drawings must be returned
approved for release within 60 days of mailing. If drawings are not returned accordingly,andlor if shipment Is delayed for any reason,the price of the
order will increase by 1.0%per month or fraction thereof for the time the shipment Is delayed.
Seller shall not be responsible for any failure to perform,or delay in performance of,Its obligations resulting from the COVID-19 pandemic or any
future epidemk,and Buyer shall not be entitled to any damages resulting thereof.
to
EESS Short Circuit and Coordination Studies
ESS Study-BidManager
SCOPE OF WORK
This quote and associated scope of work may not satisfy all requirements listed In the contract specifications.
Contact your local EESS office if you need assistance interpreting the job specifications to determine whether or not
the Bid Manager studies will meet the job requirements, or if the Bid Manager takeoff does not offer the types of
studies being requested.
The selected options for power system studies would be detailed only for proposed equipment supplied by the
Eaton sales office. New equipment supplied by others is not included. Existing or future equipment is not included.
All equipment to be covered in the study must first be completely and correctly priced into Bid Manager—before the
EESS Studies takeoff is selected and within the same Job Alternate as the study item.
The Bid Manager studies will be performed using SKM Systems Analysis software package Power*Tools for
Windows.
This quotation does not include the following:
a. Existing equipment or new equipment supplied by others
b. On-site data collection for required information on the new& existing electrical systems
c. Settings for protective relay logic, programmable logic controllers, software configuration, metering, monitoring,or
to control devices
d. Field service for start-up, testing, training or adjusting protective device settings
e. Equipment modifications for conformance to the recommendations of the proposed study
f. Study software
g. On-site project meetings
The accuracy and delivery of the study are greatly dependent upon timely receipt of accurate field information
provided by others. For an example of the types of information needed, see Generic Data Request near the end of
this document.
SHORT CIRCUITAND OVERCURRENT COORDINATION
Three-phase and line-to-ground short circuit currents would be calculated and compared to the proposed equipment
interrupting ratings down to the low voltage panelboards. This equipment evaluation table would be based on the
The Information on this document Is PREPARED BY DATE
created by Eaton.It Is disclosed In Daniel C3rfffln 9/28/2022 Eaton
confidence and It Is only to be used for
the purpose In which It Is supplied. APPROVED BY DATE JOB NAME CCUA Peon Creek wwrP
DESIGNA1ON Study
VERSION TYPE DRAWING TYPE
1.0.0.0 CHESS ST CustomerAppr.
NEG Amber Nu
ITEM Dwo$ E D.D. ITEM SHEETJVr8070W@K1 OOW At of 5
system operating configuration that produces maximum fault currents. Protective devices will have short circuit
interrupting ratings as indicated in the contract documents unless specifically listed otherwise in Eaton's Bill of
Material. Load centers and safety switches will not be covered in the studies. Existing equipment or new equipment
provided by others Is not included. For jobs where the new equipment is being Installed as part of an upgrade or
addition, only existing information regarding immediately upstream available fault current and system motor
contribution will be lump-sum/group-modeled to determine the adequacy of the short circuit ratings of the new
equipment.
Overcurrent coordination will be based on the specific protective device frame sizes shown on the contract drawings
unless specifically listed otherwise in our Bill of Material. Where only circuit breaker trip sizes and/or fuse sizes are
shown on the contract drawings, Eaton's quotation is based on the minimum frame size breaker or fusible switch
which can accommodate those trip sizes/fuse sizes unless specifically listed otherwise in our Bill of Material. Phase
and ground overcurrent coordination plots and recommended settings would be provided for the proposed Eaton
adjustable-trip protective devices.
Multi-function protective relays have many options of control, logic, metering, monitoring, virtual inputs and
configuration, but this quotation includes recommended ANSI/IEEE protective device function settings (as listed on
the contract single line diagrams)to provide adequate system protection and coordination with the equipment in the
scope of work. The customer or local installation contractor should determine any additionally required settings,
such as logic, virtual inputs and configuration. Fuses and other non-adjustable trip devices would only be shown in
the Time-Current-Characteristic (TCC) plots if they are immediately upstream or immediately downstream of an
Eaton adjustable-trip protective device that has been priced into Bid Manager.
Individual motor circuit protectors would only be shown in the TCC plots and settings table if they are immediately
downstream of an Eaton adjustable-trip circuit breaker that has been priced into Bid Manager. The contractor is
expected to use motor nameplate information to set the remaining motor circuit protectors and electronic motor
overloads. For jobs where the new equipment is being installed as part of an upgrade or addition, one level of
existing upstream and/or existing downstream overcurrent device information would be modeled to determine
overcurrent coordination with the proposed Eaton adjustable protective devices. In order to minimize the number of
to short circuit bus nodes and coordination plots,similar documentation may be used for system redundancy.
ARC FLASH STUDY
The arc flash incident energy analysis will be conducted for the proposed equipment supplied by the Eaton sales
office and listed in the Bill of Materials , down to the low voltage panelboards. Load centers are not included.
Existing equipment or new equipment provided by others is not included. The arc flash incident energy analysis will
be conducted in accordance. with the procedures stated In NFPA 70E-2018 and IEEE 1584-2018. The analysis is
performed in conjunction with the short circuit and protective coordination studies. Minimum and maximum fault
current duties and protective device clearing times are required to perform the arc flash incident energy analysis
and will be obtained from the Short Circuit and Protective Device Coordination studies.
Results of the arc flash study are used to define the flash boundary and the incident energy at electrical distribution
equipment locations as defined by the scope of work. Safe working distances will be specified for calculated fault
locations based upon the calculated arc flash boundary considering an Incident energy of 1.2 caUcm2. To ensure
conservative results and a consistent approach in the adoption of IEEE 1584-2018, Eaton's power systems
engineering group has defined standard electrode configurations, equipment dimensions, and bus bar gaps that will
be used for all equipment to be included in the arc flash incident energy analysis. If the calculated incident energy at
some equipment locations is unacceptable to the customer, further investigation, outside the scope of this study, is
The Information on this document le PREPARED BY DATE
crested by Eaton.It is disclosed In I Daniel Griffin 9/28/2022 Eaton
confidence and It is only to be used for
the purpose In which h le supplied. APPROVED BY DATE JOB saw CCUA Peters Creek WNTP
DESIDNATION Study
VERSION TYPE DRAINING TYPE
1.0.0.0 CHESS_ST Customer Appr.
NEO-ALT NLnr REVISION DWE SIZE MD. REM SHEET
JV IIDTosx2K7-0SSS A 2 of
recommended to determine the most effective means of reducing the incident energy while maintaining the highest
desired degree of reliability.
PE REVIEW/STAMP
Upon completion of the analysis report, a PE Review/Stamp will be provided by a registered professional engineer
in the selected state or province(from drop-down menu)
STUDY LEAD TIMES
Lead time for job-specific data request=within 2 weeks of receipt of one-line, specifications,detailed bill of material,
and vista order paper.Lead time for final study results = 4-6 weeks after all remaining data received,
includingequipment submittals and answers to job-specific data request.
REPORT/STUDY RESULTS
Maximum of four hardcopies using permanent velo binding system or emailed report file submittal would include the
following.
1. Introduction describing the background, objectives,and scope of the study
2. Executive summary with clear, concise conclusions and recommendations
3. Philosophy and basis of each analysis module that was chosen and priced within Bid manager
4. Short circuit data and calculations
to
5.Table comparing calculated short circuit duties and protective device interrupting ratings
6.Coordination time-current plots of protective device curves and associated single line
7. Table listing coordinated settings for adjustable-trip protective devices
8. Selective coordination evaluation surY maly table(if chosen arid priced)
9.Arc flash incident energy analysis summary table(if chosen and priced)
10.Arc flash labels(if chosen and priced)
11.System single line diagram per latest version of SKM Power*Tools for Windows software
Report revisions that are required due to project changes or incorrect information that was provided to Eaton's
Power Systems Engineering group would require an appropriate change order.
GENERIC DATA REQUEST
The Infonnadon on this document Is PREPARED BY DATE
meted by Eaton.It Is disclosed In Daniel Gann 9/28/2022 Eaton
confidence and It is only to be used for
the purpose In which It Is supplied. APPROVED BY DATE JOB NAF.E CCUA Peters Creek wwrp
DESIQNATION Study
VERatoN TYPE DMIMNOTYPE
1.0.0A CHESS ST CuelomerAppi
NEQ.LLTNumber REVISION DING BIB Q.O. IT M MEET
JvraoToexan.oaoa A 3 of 5
In order to prepare an official Data Request, need legible copy of single line diagrams, accurate Bid Manager file
containing all proposed equipment, and interunit order paper for the study. Others would supply necessary data for
the electrical system, for example:
EATON'S PROJECT GROUP
1. Complete end up-to-date information on Eaton equipment being provided.
2.Accurate factory drawings for all MVA, MVS,Ampgard, and LVA switchgear.
3. Legible copy of electrical single line diagrams
4. Transformer schedules
5. Motor control center horsepower schedules
UTILITY
1. Utility contact name, phone number, and email address
2. Utility three-phase& line-to-ground fault current with associated X/R ratios& system voltage
3. Utility transformer primary fuse manufacturer, type,amp rating, and speed rating
4.Utility transformer winding (delta-wye ground, etc.), kVA rating, impedance%Z, kV ratings
ELECTRICAL CONTRACTOR
to 1. Using contract one-line or riser diagram as reference, provide cable lengths, phase conductor sizes (AWG,
MCM), # of sets per phase, types (AL or CU), whether single-conductor cable or three-conductor cable, and
whether raceway is Magnetic or Non-magnetic.
2. If customer owns incoming transformer:winding (delta-wye ground,etc.), kVA rating, impedance%Z, kV ratings.
3. If customer owns incoming transformer: primary fuse manufacturer, type, amp rating, and speed rating.
4.Generator submittal including X"d reactances, current decrement curve, and withstand curve
5. Generator local-mounted breaker manufacturer, type, ampere rating, trip unit type, functions
8. Non-Eaton supplied ATS manufacturer,type, ampere rating, &short circuit withstand rating
7.If any Chillers, Elevators, AHU's, AC's, or RTU's, need motor horsepower rating, and if not indicated - where
connected to system single line diagram
8. Summary of any additional motor hp that may be connected to distribution panels but not shown on single line or
riser diagram
The Information on this document Is PREPARED EY DATE
emoted by Eaton.It Is disclosed In Daniel Griffin 9/2g/2022 Eaton
confidence and It Is only to be used for
the purpose In whkh It la supplied. APPROVED BY DATE JOB NAME CCUA Peters Creek WWTP
DESIGNATION Study
VERSION 1 TYPE DRAWING TYPE
1.0.0.0 CHESS_ST Customer Appr.
NEG•ALTNumber REVISION DWG SIZE G.D. ITEM SHEET
M90706X2IC1.0009 A 4 of 6
9. For other than Eaton supplied fuses: manufacturer,type, catalog number,and ampere rating
10. For existing overcurrent devices that are immediately upstream or downstream of the proposed Eaton
equipment (if circuit breakers need manufacturer, type, plug rating, trip unit type, existing adjustable settings, &
setting ranges, if fuses need manufacturer, type, catalog number, and ampere ratings, If relays need phase and
ground overcurrent relay manufacturers, style numbers, phase and ground CT ratios, existing adjustable settings,
and setting ranges)
Notes:
Comments Clarifications:
to
The Information on this document Is PREPARED BY DATE
crested by Eaton.It is disclosed In Danlel Griffin arisi2022 Eaton
confidence and It le only to be used for APPROVED BY DATE JOB NAVE CCUA Peters CreekyYYVTP
the purpose In which it Is supplied.
DEe1GNAT1ON Study _
VERSION TYPE DRAYANS TYPE
1.0,0.0 CHESS ST Customer Appr.
NEG.ALTWits? Revis N I DIM WYE O. REM SNIT
JVT3O7oex Ciaooa IE A 506
Comments & Clarifications
EESS Start-up
to
1
MCC General Information
MCC General information Ind.Light Type 8v Xfmr
Wiring Diagram Type Eaton Standard MCC Quantity Structure Schedule
Standards UL845,NEMA,NEC There are 2 structure(s).
Special Codes UL All structures have a 600 A vertical bus.
Service Voltage(3 Phase) 480 Total width of all sections Is 40"
Frequency 60 Height of all sections Is 91"
SYsiere 3PH3W
Witness Testing No Unit Modifications
Service Entrance Label
Enclosure Specifications
Total2
NEMA 1 Gaaketed
Depth 21"Front Mt Only
Height 90"
Horizontal Wireways 9"High,Top&Bottom
Vertical Wireways 4"
Channel Sills Yes
Bottom Plates None
150 Watt Space Heaters No
Space Heater Thermostat 1
Master Terminal Block Location None
IBC/CBC Seismic Qualified No
ABS Certified No
Sus System Specifications
Main Bus Amps 800
Main Bus Material Copper
Main Bus Bar Plating Tin
Insulated Hortz.Bus No
1000A/sq in.Cu Bus No
Vertical Bus Amps See Structure Schedule
Vertical Bus Material Tin Plated Copper
Vertical Bus Barrier Labyrinth,Isolated/
Insulated with shutters
to Bus Bracing 85,000
Ground Bua 300
Ground Bus Location Bottom
Ground Bus Lug Size 146-350Kcrnll
Ground Bus Lug Type Screw
Plug-In 300A Vert.Gnd.Bus No
Neutral None
Horizontal Bus Temperature Rise 85 deg C
Bottom Vert.Bus Barrier Yes
Vertical Ground Bus No
Incoming Line Termination
Device:NGH-C Main Bkr(B00A trip),Lugs:444/0-500Kcmli
Cable Entry Bottom
Splice Kit/Transition None
MCC Type Match Up
MCC Type Match Up GO# "None'"
MCC Starter Specifications
Wring Class 2B
Control Voltage 120
Control Voltage Src Ind CPT
Nameplate Size 1"X 2.5"
Nameplate Color Black/White Letters
Pilot Day.Model 10250T
The information on this document le PROD EY DATE Fayetteville,NC
crested by Exton Corporation.It Is Druid Griffin waeno22 Eaton Y
disclosed In confidence and It Is only to ��NArsE CCUAp Creek yyyy�p
be used for the purpose In which Ills
supplied. DESIGNATION _ MCC-MAJN•1
VERSION TYPE DRAWN°TYPE
1.6.2.8 Freedom+MCC Customer Appr. —
NEG-ALT Numbw REVISION DWG SIZE G.O. nu SHEET
JV730706X2K1-0003 A _ _ t 1 of 3
Top View
5.411 5.41
17. E
• •1 I '"`- 11E71-
1F 2F
A .•
B SPD
C
D
G
Sub Feed
H
1
K
to L
M JGH-C3B01
20.156*20.078)
1.25 1.25
E- ->
0
co. In 1111
N CO
20.156 20.078
Floor View
The Information on this document Is PREPARED m' DATE
created by Eaton Corporation.It Is Daniel Griffin 9128►2022 Eaton Fayetteville, NC
disclosed In confidence and It Is only to PPPRCVFD eY DATE JOaNAaE CCUAPetua Creek MEP
be used forth.purpose In which It is
supplied. DEamourrIDN MCC•MAIN-1
VERSION TYPE DRAWING TYPE
1.0.2.8 Freedom+MCC Customer Appr.
NE6-ALTNumber REVIewN Dwotia 4a
rrEM 6Ftr
Jv7367o6KiK1-00o11 A 1 2 of 3
WI Nanm mats cia8e Starter.Size May Unit
HP_/El9 Poles Features
'Mte_la Ido/Cug. 12
1M NCi-i-C Main Bkr NGH-C 1 Main Bkr Auxiliary Interlock 1NO-
INC
(800A trip),Lugs: 3P 1 Alarm Contact Circuit Breaker Sw.
4-#410500Kcmll NONE 800 1 Main Bkr Shunt Trip
1 RMS310+ALSlGTt w/GF
2B 300KA,SPD Standard
+Surge Counter
Features Package,with NONE
Circuit Breaker _
2D 12"Door
2F 12"Door
2M #1/0-750 Kcmll 4/Ph
Sub Feed Lugs
(Screw) NONE
to
The Information on this document Is PREPARED BY DATE
crested by Eaton Corporation.It Is Denial Griffin 9/28/2022 Eaton Fayetteville,NC
disclosed in confidence and It Is only to —be used for the purpose In which It Is APPROVED BY DATE JOB NAME CM/Afters Creek WWTP
supplied. DESIGNATION MCC-MAIN-1
VERSION TYPE DEAYYNE'TYPE
1.0.2.8 Freedom+MCC Customer Apr..
NEO-ALTNumber REVISION DWG a El0.0. ITEM I him
JVTe410B%7Klaooi A 3 of 3
R ,
MCC General Information
MCC General information Ind.Light Type 8v Xfmr
Wring Diagram Type Eaton Standard MCC Quantity Structure Schedule
Standards UL845,NEMA,NEC There are 3 structure(s).
Special Codes UL All structures have a 800 A vertical bus.
Service Voltage(3 Phase) 480 Total width of all sections Is 80"
Frequency 80 Height of all sections la 90"
System 3PH3W
Witness Testing No Unit Modifications
Enclosure Specifications Service Entrance Label
Total Structures 3
Type NEMA 1 Gasketed
Depth 21"Front Mt Only
Height 90"
Horizontal Wireways 9"High,Top&Bottom
Vertical Wireways 4"
Channel Sills No
Bottom Plates None
15D Watt Space Heaters No
Space Heater Thermostat 1
Master Terminal Block Location None
IBC/CBC Seismic Qualified No
ABS Certified No
Bus System Specifications
Main Bus Amps 2000
Main Bus Material Copper
Main Bus Bar Plating Tin
Insulated Hertz.Bus No
1000A/sq In.Cu Bus No
Vertical Bus Amps See Structure Schedule
Vertical Bus Material Tin Plated Copper
Vertical Bus Barrier Labyrinth,Isolated/
Insulated with shutters
tO Bus Bradng 85,000
Ground Bus 800
Ground Bus Location Bottom
Ground Bus Lug Size 1fi8-350Kcmll
Ground Bus Lug Type Screw
Plug-In 300A Vert.Gnd.Bus No
Neutral None
Horizontal Bus Temperature Rise 85 deg C
Bottom Vert.Bus Barrier Yes
Vertical Ground Bus No
Incoming Line Termination
Device:RGH-C Main Bkr(2000A trip),Lugs:8-#2-800Kcmll
Cable Entry Bottom
Splice Kit/Transition None
MCC Type Match Up
MCC Type Match Up GO# "None
MCC Starter Specifications
Wiring Class 2B
Control Voltage 120
Control Voltage Src Ind CPT
Nameplate Size 1"X 2.5"
Nameplate Color Black/White Letters
Pilot Dev.Model 10250T
The Information on this document Is PREPARED BY DATE
created by Eaton Corporation.It is Daniel Griffin Damon Eaton Fayetteville, NC
disclosed in confidence and It h only to
bs used for the purpose In which k Is APPROVED BY DATE Boa NAME CCUA Patera Creek WVVrP
supplied. DESIGNATION MCC-MAIN-2
VERSION TYPE DRAVANOTYPE
1.02.11 Freedom+MCC Customer Appr.
NED-AST Numbr REVISION DWG 81zE G.O. nail SHEET
Arr3oloex2ni-0003 A 1 of 3
Top View
5.411 5.41 5.411
{ 1f. > t 1r. > 4C17. >
1F 2F 3F
A
14.4,44
B SPD Sub Feed
C
D
F
G
H
J
K
to L
M RGH-C320C
20.156' -_ 20.078 - 20.078'
1.25 1.25 1.25
a
r
fV m
1,11,111111
_
20.156 20.078 20.078
Floor View
The Information on this document Is PREPARED BY DATE
created by Eaton Corporation.it Is Daniel Griffin ei a, o22 Eaton Fayetteville, NC
disclosed in confidence and It le only to —
be used for the purpose In which It la APPR0VED BY DATE JOS NAME CCUA Peters Creek WNTP
supplied. DESIGNATION MCC-MAIN-2
VERSION TYPE DRAWING TYPE
1.D,2.8 Freedom+MCC CustonwrAppr.
NEG-ALTNumbr REVISION DYI G.O. ITFY MEET
JVrhOTDb%I(1.0003 ..- A - - — 2 of 3
Unit Nemola laudation Clan Starter Size Maw Unit
HP/FLA Eska E
E81Dlaa. Trio/Clio
1M RGH-C Main Bkr RGH-C 1 Main Bkr Auxiliary Interlock 1 NO-
1NC
(2000A trip),Lugs: 3P 1 Alarm Contact Circuit Breaker Sw.
8-02-800Kcmli NONE 2000 1 Main Bkr Shunt Trip
1 RMS 310+ALSIG Tit vd GF
2B 300KA,SPD Standard
+Surge Counter
Features Package,with NONE
Circuit Breaker
2D 12`Door
2F 12"Door
2H _ 12"Door
2K 12"Door
2M 1r Door
3M 81/0-750 Kcmll 0/Ph
Sub Feed Lugs
(Screw) NONE
tO
'The Informsfion on this document Is PREPARED BY DATE
crested by Eaton Corporation.It Is Daniel Griffin 9/2s/2o22 Eaton Fayetteville,NC
disclosed In confidence and It Is only to be used for the purpose In which It Is APPROVED BY DATE JOB NAM CCUA Peters Creek W NTP
supplied. DESIGNATION MCC-WJN-2
VERSION TYPE DRAWING TYPE
1A.2.E Freedom+MCC CustomerAppr.
NEO-ALT Num*v REVISION DWG OA. ITEM SHEET
JV73070612K1.0000 f S1A _ _ 3 of
MCC General Information
MCC General information Ind.Light Type By Xfmr
Wring Diagram Type Eaton Standard PL Color(On) Red
MCC Quantity PL Color(Off) Green
Standards UL845,NEMA,NEC
Special Codes UL Structure Schedule
Service Voltage(3 Phase) 480 There are 5 structure(').
Frequency 80 All structures have a 800 A vertical bus.
System 3PH3W Total width of all sections is 108"
Wtness Testing No Height of all sections Is 91"
Enclosure Specifications Unit Modifications
Total Structures 6 #18awg,MTW Control Wre
Type NEMA 12 Dust tight Terminal Block-Latching Pull-Apart.Std.
Depth 21'Front Mt Only Wlremarker$at Each End
Height 90" Coll Surge Suppressor
Horizontal Wireways 9'High,Top&Bottom
Vertical Wlreways 4"
Channel Sills Yes
Bottom Plates Standard
150 Watt Space Heaters No
Space Heater Thermostat 1
Master Terminal Block Location None
IBC/CBC Seismic Qualified No
ABS Certified No
Bus System Specifications
Main Bus Amps 800
Main Bus Material Copper
Main Bus Bar Plating fin
Insulated Horiz.Bus No
1000A/sq In.Cu Bus No
Vertical Bus Amps See Structure Schedule
Vertical Bus Material fin Plated Copper
Vertical Bus Barrier Labyrinth,Isolated/
to Insulated with shutters
Bus Bracing 85,000
Ground Bus 300
Ground Bus Location Bottom
Ground Bus Lug Size 1-#8-350Kcmi1
Ground Bus Lug Type Screw
Plug-in 300A Vert.Gnd.Bus No
Neutral None
Horizontal Bus Temperature Rise 85 deg C
Bottom Vert.Bus Banter Yes
Vertical Ground Bus No
Incoming Line Termination
Device:'None"
Cable Entry Bottom
Splice Kit/Transition None
MCC Type Match Up
MCC Type Match Up GO# ""None""
MCC Starter Specifications
Wring Class 2B
Control Voltage 120
Control Voltage Src Ind CPT
Nameplate Size 1"X 2.5"
Nameplate Color Black 1 White Letters
Pilot Dev.Model 10250T
The Information on this document Is I PREPARED BY DATE
created by Eaton Corporation.It is Daniel Griffin 9/28/2022 Eaton Fayetteville, NC
disclosed In confidence and It Is only to
be used forth'purpose In which It Is APPROVED BY DATE JOB NAME CCUA Peters Creek WWIP
supplied. oesiONATION MCC-1
VERSION TYPE DRAtMNOTYPE
1.0.2.8 Freedom+MCC CuMemerAppr.
NEO-ALT Number REVISION DWG ME OA. rEM SHEET
JV73070SX2K1-o0o3 A I 1 of 5
Notes/Special Instructions
PROVIDE EATON D65 3 PHASE VM IN METERING UNIT WITH OUTPUT CONTACTS RUN TO TB.
5B TO BE WIRED TO 42 CKT PANELBOARD. SHALL BE 208V 3 PH RATED
WIRE 5E CONTACTOR LINE SIDE FROM 3 POLE BREAKER IN Li. WIRE LOAD OF CONTACTOR TO MLO IN
PANEL L1 SECTION 2.
METER TO BE PXM2280
to
The Information on this document Is PREPARED BY DATE
crested by Eaton Corporsdon.k h Daniel Orlin 0!21112022 Eaton Fayetteville, NC
disclosed In confidence and It I.only to
be used for the purpose In whkh k IS APPROVED BY DATE JOB NAfeE CCUA Peters Creek WW1P
supplied. DESIGNATION MCC-1
VERSION TYPE DRAWNO TYPE
1.0.2.E Freedom+MCC Customer Appr.
NEG-ALT Number REVISION Owe elm G.O. MTEM SHEET
JV73D700X2K1.0003 A 2 0f8
Top View
•
5.41 5.�41 � 5.41 5.41 5.41
F 21. �—TT. (it 21.d > TL
1F 2F 3F i 4F 5F
A illini42CKT
B ATS SPDMFD100/10 SPD
C . II I Milli
D 1 kiFD100110
E MTR FVC S3
F �1111E11 _____ 18CKT
G f IFD50/1IXWM ii
HMil
J
K
1. 1
to L
M LGH3800 45KVA
.1-,_:
24.15r• 20.078><20.078 24.078 24.078 20-078
1.25 1.25 1.25 1.25 1.25
-F ->F -F -F -E—
A _ ,
oar
CI; US 1.25 1.25 1.25 1.25 1 25
Nr < I, x� x- x�r x >
24.158 20.078 20.078 24.078 20.078
Floor View
The Information on this document is PREPARED BY DATE
created by Eaton Corporation.It Is Daniel Griffin f,°28,xoz2 Eaton Fayetteville, NC
disclosed In confidence end It Is only to .
-
be used for the purpose In which It Is APPROVED BY DATE JOEI NAM CCUA Peters Creek WWTP
supplied. DESIGNATION MCC-1
VERSION TYPE DRAINING TYPE
1.0.2.8 Freedom+MCC Customer App..
NEO-ALTNumber REVISION DWG SIZE 0.0. ITEM SHEET
.Iwa0705x2K1.0003 A 3 of 5
link Nam= Deacrintlon Class Starter SIg Bkr/Sw Sjp]t
11P/FLA P9JQa
Wire Dfao. Trto/Clip
1164 Eaton Automatic 1 ATC-900 controller
Transfer Sw.,ATV9, 1 34c.Logic Extender Cable 98"
800A,3P,ATC-900 NONE 1 14c.Aux Relay Contacts Normal
controller Source vallable(4 Form C)
1 14d.Aux Relay Contacts
Emergency Source Available(4
Form C
•
2B 300KA,SPD Standard
+Surge Counter
Features Package,with NONE
Circuit Breaker
2E PXM2270
NONE
2GL HFDTw In Bkr(50A HFD
/100A trip) 3P
5599A85.DWF 50
2GR HFDTWin Bkr(50A HFD
/100A trip) 3P
5599A85.DWF 100
2M LGH Bkr(500A trip) LGH
3P
281473.DWF 800
3BL HFDTWin Bkr(100A HFD
/100A trip) 3P
5599A85.DWF 100
3BR HFDTWin Bkr(100A HFD
/10oAtrip) 3P
5599A85.DWF 100
3DL HFDTwin Bkr(100A HFD
/100A trip) 3P
5599A85.DWF 100
3DR HFDTwin Bkr(100A HFD
/100A trip) 3P
to 5599A85.DWF 100
3F 12"Door
3H 12"Door _
3K 12"Door
3M 12"Door
4F Ll PL1A Panelboard 80 Pnlbd Bkr,BAB 1 Pole 20A bkr
225A 120/208V 3PH
4W 42 CKT 5A10398.DWF
4M 45 Kva 3 ph,440-480
I 120-208V High
Efficiency Xfmr,70A Pri., 5A10398.DWF
175A Sec.Bkr.
5B 100KA,SPD Standard
+Surge Counter
Features Package,with NONE
Circuit Breaker
5E FVC Contactor Size F208 3 Tm.Brk. 1 150VA Individual CPT,Fused
3[TM Ckt Brk] 50KW 3P 1 N.O.Starter Aux Contacts,Slze 1-4
NONE 90 1 N.C.Starter Aux Contacts,Size 1-4
1 Motor Load Block(100A)
1 Pilot Light-10250T-LED(On)
1 Pilot Ught-10250T-LED(Off)
1 3 Poe.Sel.Sw.,10250T(Hand-Off-
Auto)
5J L1 PL1A Panelboard 18 Pnlbd Bkr,BAB 1 Pole 20A bkr
SECTION 2 100A 120/208V 3PH
The information en this document Is PREPARED IT DATE
crated by Eston Corporation.It to Daniel Griffin 9/28/2022 Eaton Fayetteville,NC
disclosed In confidence and It Is only to
be used for the purpose In which It Is APPROVED BY DATE JOB NAME CCUA Peter Creek WWTP
supplied. DESIGNATK1N MCC-1
VERSION TYPE DRAWING TYPE
1.0.2.13 Freedom+MCC l Customer Appr.
I NEO-ALTNumb.r REVISION DWO SRE 0.0. ITEM SHEET
JV73e7eex2K1.00c3 A 4 of 6
Unit N8Mifipliikt 12=12112n Class Starter Stu IRON Unit
HP/ELA PQ Features
tore Dfep. Trip/CliQ
4W 18 CKT 5A10398.DWF
5K 8"Door
5M 12"Door
tO
The information on this document Is PREPARED BY DATE
crusted by Eaton Corporation.It is Daniel&tiin eramO22 Eaton Fayetteville, NC
disclosed In confidence end It Is only to -
be used for the purpose In which it is APPROVED BY DATE JOB NAME CCUA Peters Creek YVIATTP
supplied. DESIGNATION MCC-1
VENISON TYPE DRAUANGTYPE
1.D.2.13 Freedom+MCC CustomerAppr.
NEGAI.TNumber REVISION DWDSIZE O.C. ITEM SHEET
JV73D796x2K1-00o3 A 5 of s
MCC General Information
MCC General information Nameplate Color Black!White Letters
Wiring Diagram Type Eaton Standard Pilot Dev.Model 10250T
MCC Quantity Ind.Light Type 8v Xfrnr
Standards UL845,NEMA,NEC PL Color(On) Red
Special Codes UL PL Color(OR) Green
Service Voltage(3 Phase) 480 Frequency 60 Structure Schedule
System 3PH3W There are 7 structure(s).
Witness Testing No Structure(s)2,4,6,8,7 have a 800 A Vertical Bus.
Structure(s)3 have a 800 A Vertical Bus.
Enclosure Specifications Structure(s)1 Have No Vertical Bus.
7 Total width of all sections Is 144"
TotalTYPe Structures NEMA 12 Dust tight Height of all sections Is 91"
Depth 21"Front Mt Only Height 90" Unit Modifications
Horizontal WIrewaya 9"High,Top&Bottom #16awg,MTW Control Wire
Vertical Wlreways 4" Terminal Block-Latching Pull-Apart,Std.
Channel SiNs Yes Wlremarkers at Each End
Bottom Plates Standard Coll Surge Suppressor
150 Watt Space Heaters No
Space Heater Thermostat 1
Master Terminal Block Location None
IBCICBC Seismic Qualified No
ABS Certified No
Bus System Specifications
Main Bus Amps 2000
Main Bus Material Copper
Main Bus Bar Plating Tin
Insulated Horiz.Bus No
1000A1sq in.Cu Bus No
Vertical Bus Amps See Structure Schedule
Vertical Bus Material Tin Plated Copper
Vertical Bus Barrier Labyrinth,Isolated!
Insulated with shutters
to Bus Bracing 65,000
Ground Bus 800
Ground Bus Location Bottom
Ground Bus Lug Size 146-350Kcmil
Ground Bus Lug Type Screw
Ping-in 300AVert.Gnd.Bus No
Neutral None
Horizontal Bus Temperature Rise 65 deg C
Bottom Vert.Bus Barrier Yes
1 Vertical Ground Bus No
Incoming Line Termination
<Text coiumnspan "2">Device:01/0-750
Kcmll 8/Ph Main Lugs(Screw)&CTec/
Text>
Cable Entry Bottom
Splice Kit!Transition None
MCC Type Match Up
MCC Type Match Up GO# ""None"'
MCC Starter Specifications
Wring Class 2B
Control Voltage 120
Control Voltage Src Ind CPT
Nameplate Size 1"X 2.5"
The Information on this document Is PREPARED BY DATE
created by Eaton Corporation,h le Daniel G:rrnn sr2sr2022 Eaton Fayetteville, NC
be used
f r the
and is onlyf to APPROVED BY DATE JOB NAME CCUA Paters Creek WWTP
be used for the purpose M which k is
supplied. DE610NATIIXd MCC-2
VERSION TYPE DRANINO TYPE
1.0.2.8 Freedom+MCC Customer Appr.
NEG-ALT Number REVISION DNA 9 OD. - — 'ITEM SHEET
,iVTISTO6X2RI-06112 A l 1 of 5
Notes/Special Instructions
PROVIDE EATON D65 3 PHASE VM IN METERING UNIT WITH OUTPUT CONTACTS RUN TO TB.
7B TO BE WIRED TO 42 CKT PANELBOARD. SHALL BE 208V 3 PH RATED
WIRE 7E CONTACTOR LINE SIDE FROM 3 POLE BREAKER IN Li.WIRE LOAD OF CONTACTOR TO MLO IN
PANEL L1 SECTION 2.
METER TO BE PXM2280
to
The Information on this document Is PREPARED EV DATEI
created by Eaton Corporation.It is Daniel Griffin tu2er2022i Eaton Fayetteville,NC
disclosed In confidence end It Is only to be used for the purpose In which it is APPRovED m' a►EI JOB NAME CCUA Peters Creek WWTP
supplied. DESIGNATION MCC-2
VERSION TYPE DRAWING TYPE
1.0.2.2 Freedom+MCC Customer Appr.
NEG-ALTNimbir REVISION DWG SIZE 0.0. ITEM SHEET
Jvr1oTo672K140011 A 2 of 5
Top View
5.�41 5..y41I 5.41 5.4,1 5.4,1 5.4.1 5..4,1
-rr3'- < 1T.6; � T.1 17,i> < 21.1 <IT.
1F 2F 3F 4F 5F 8F 7F
42CKT
B MLO l SPD II SPD
7
C 7iFD3050 is
D � C--
'''. ri
E bMTR HFD3100 I HFD3050 FVC S3
F 18CKT
G HFD3100 HFD3050 HFD3100
H ill 1 11 31
J
K
to L
M HMDL360QHMDL360 HMDL 1 MDL360 45KVA
<20.156*20.078 20.078 20.078�20.078>l< 24.07E 20.078"J
1.25 1.25 1.25 1.25 1.25 1.25 1.25
-+ore- -F -E -!F —!F -F -F
A l
O�—
ci co 1.25 1.25 1.25 1.25 1.25 1.25 1.25
F am - � -+ � -> F F -> F y y y y
, � X� )- _�)_
<F ),< ›ic
>
20.158 20.078 20.078 20.078 20.078 24.078 20.078 1
Floor View
The Information on this document Is PREPARED BY DATE
crested by Eaton Corporation.It Is Daniel Griffin 9/25/2022 Eaton Fayetteville, NC
disclosed in confidence and It Is only to —
be used for the purpose in which it is APPROVED" DATE JOB NAME CCUA Peters Creek NANTP
supplied. DESIGNATiON MCC-2
VERSION TYPE DRAWING TYPE
1.0.2.6 Freedom+MCC CustomerAppr.
NEG-ALTNumber REVISION I DWG SIZE G.O. .REM SHEET
JV73070EX2K1.0003 A 3 of 5
Unit Nameplate 12§§statirin Qla§B Starter Stze Bkr/Sw Una
HEELS Poles Features
Wire Diag. Lisl;!Glig
1 M *110-750 KCmlI 8/Ph - -
Main Lugs(Screw)
&CTs NONE
2B 300KA,SPD Standard
+Surge Counter
Features Package,with NONE
Circuit Breaker
• 2E PXM2270
NONE
2G 12"Door _
2M HMDL Bkr(800A trip) HMDL
3P
281473.DWF 800
3C 18"Door
3E HFD Bkr(100Atrip) HFD 1 Motor Load Block(100A)
3P
NONE 100
3G HFD Bkr(100A trip) HFD 1 Motor Load Block(100A)
3P
NONE 100
3M HMDL Bkr(800A trip) HMDL
3P
281473.DWF 800
4A 8"Door
4C HFD Bkr(50A trip) HFD 1 Motor Load Block(100A)
3P
NONE 50
4E HFD Bkr(50A trip) HFD 1 Motor Load Block(10DA)
3P
NONE 50
4G HFD Bkr(50A trip) HFD 1 Motor Load Block(100A)
3P
NONE 50
to 4M HMDL Bkr(800A trip) HMDL
3P
281473.DWF 800
5B 12"Door
5E 18"Door
5G HFD Bkr(100Atrip) HFD 1 Motor Load Block(100A)
3P
NONE 100
5M HMDL Bkr(600A trip) HMDL
3P
281473.DWF 800
8F L2 PL1A Panelboard 42 Pnlbd Bkr,BAB 1 Pole 2 -bkr
225A 120/208V 3PH
4W 42 CKT 5A10398.DWF
6M 45 Kva 3 ph,440-480
/120-208V High
Efficiency Xfmr,70A PrI., 5A10398.DWF
175A Sec.Bkr.
7B 100KA,SPD Standard
+Surge Counter
Features Package,with NONE
Circuit Breaker
7E FVC Contactor Size F208 3 Tm.Brk. 1 160VA Individual CPT,Fused
3[TM Ckt ark] 50KW 3P 1 N.O.StarterAux Contacts,Size 1-4
NONE 90 1 N.C.Starter Aux Contacts,Size 1-4
1 Motor Load Block(100A)
The Information on this document Is BARED BY DATE
created by Eston Corporation.tt Is Daniel07Mb+ e/2e/2022 Eaton Fayetteville,NC
disclosed in confidence and It I.only to —
he used for the purpose in which it is APPROVED BY DATE JOB NAME CCUA Peters Creek WWrP
supplied. otakowknON MCC-2
VERSION HYPE DRAMA TYPE -.
1.0.2.8 Freedom+MCC CustomerAppr.
NEG-ALTNumbar REVISION DWOSIZE O.O. Irim SHEET
Mek17O5x2K1.0008 A 4 of 5
Unit Noma& D otfon flea Starter Slze filsaty Unit
HP/FLA aka Features
Yll re Dlaa. Trio/CIIp
1 Pilot Light-10250T-LED(On)
1 Pilot Light-10250T-LED(Off)
1 3 Pos.Sal.Sw.,10250T(Hand-Off-
Auto
7J L2 PL1A Panelboard B0 Pnlbd Bkr,BAB 1 Pole 20A bkr
SECTION 2 100A 120/208V 3PH
4W 18 CKT 5A10398.DWF
7M 18-Door
to
The Information on this document Is PREPARED BY DATE
crested by Eston Corporation.It le L:nil Griffin W2t/2O22 Eaten Fayetteville,NC
disclosed In confidence end it is only to .- —
be used for the purpose In which It I. APPROVED BY DATE JOB NAME CCUA Peters Creek 1NWTP
supplied. DESIGNATION MCC-2
VERSION TYPE DRAMS TYPE
1 1,0.2.8 Freedom+MCC CustomerAppr.
NEO-ALTNumber REVISION DWOSIZE O.O. ITEM SHEET
JV770706X2K1.0003 A 6 of 5
MCC General Information
MCC General Information Ind.Light Type 6v Xfmr
Wiring Diagram Type Eaton Standard PL Color(On) Red
MCC Quantity PL Color(Oft) Green
Standards UL845,NEMA,NEC
Special Codes UL Structure Schedule
Service Voltage(3 Phase) 480 There are 3 structure(s).
Frequency 80 All structures have a 800 A vertical bus.
System 3PH3W Total width of al sections Is 84"
Witness Testing No Height of all sections Is 91"
Enclosure Specifications Unit Modifications
Total Structures 3 #18ewg,MTW Control Wire
Type NEMA 12 Dust tight Terminal Block-Latching PulH4part,Std.
Depth 21"Front Mt Only 1Mremarkers at Each End
Height 90" Coll Surge Suppressor
Horizontal Wlreways 9"High,Top&Bottom
Vertical Wlreways 4'
Channel Sills Yes
Bottom Plates Standard
150 Watt Space Heaters No
Space Heater Thermostat 1
Master Terminal Block Location None
IBC/CBC Seismic Qualified No
ABS Certified No
Bus System Specifications
Main Bus Amps 600
Main Bus Material Copper
Main Bus Bar Plating Tin
Insulated Horiz.Bus No
1000A/sq in.Cu Bus No
Vertical Bus Amps See Structure Schedule
Vertical Bus Material Tin Plated Copper
Vertical Bus Barrier Labyrinth, Isolated/
to Insulated with shutters
Bus Bracing 85,000
Ground Bus 300
Ground Bus Location Bottom
Ground Bus Lug Size 1-06-350Kcmil
Ground Bus Lug Type Screw
Plug-In 300A Vert.Gnd.Bus No
Neutral None
Horizontal Bus Temperature Rise 65 deg C
Bottom Vert.Bus Barrier Yes
Vertical Ground Bus No
Incoming Line Termination
Device:#4-350 Kcmil 4/Ph Main Lugs(Screw)
Cable Entry Bottom
Splice Kit/Transition None
MCC Type Match Up
MCC Type Match Up GO# "None
MCC Starter Specifications
Wiring Class 2B
Control Voltage 120
Control Voltage Src Ind CPT
Nameplate Size 1"X 2.5"
Nameplate Color Black/Whlte Letters
Pilot Dev.Model 10250T
The Information on this document la PREPARED BY DATE
crested by Eaton Corporation.It is Daniel Gruen 9128/2022 Eaton Fayetteville,NC
disclosed in confidence sad It Is only to
be mad for the purpose In whkh k la APPROVED BY DATE JOB NAME CCW1Patere Creek WNW
supplied. DESIGNATION MCC-7
VERSION TYPE DRAWING TYPE
1.0.2.e Freedom+MCC _ Customer Appr.
BEG-ALTNumber REVISION DWGS2E G.O. ITEM SHEET
JVT307011X2K1.0003 A 1 of 4
NoteslSpeclal Instructions
3F TO BE WIRED TO 42 CKT PANELBOARD. SHALL BE 2O8V 3 PH RATED
WIRE 2D CONTACTOR LINE SIDE FROM 3 POLE BREAKER IN L2.WiRE LOAD OF CONTACTOR TO MLO IN
PANEL L3 SECTION 2.
to
The information on this document is PREPARED BY DATE(
crested by Eaton Corporation.lt k Daniel Griffin 8/28/2022 Eaton Fayetteville, NC
disclosed In confidence and It is only to be used for the purpose in which it Is APPROVED BY DATE1 JOB NAME CCUA Peters Creek WIMiP
supplied. DESIGNATION MCC-7
♦ VERSION TYPE DRAWING TYPE -_
7.0.2.8 Freedom+MCC Customer Appr.
NEG-ALT NumMr REVISION DM SIZE G.D. REM SHEET
JV7307O8X2X1-c003 A 2 of 4
Top View
tt�'�114�1�ti rilk� ��
1F 2F 3F
A 42CKT
C
D FVC S3
E 18CKT
F SPD
•
H HFD3100
MLO Sub Feed
K
L
to
ell 30KVA
24.156 20.078*20.078
1.25 1.25 1,25
E- ->•F E—
0
N m_
24.156 20.078 20.078
Floor View
The Inknnit on on this document Is PREPARED SY DATE
created by Eaton Corporation.It Is Daniel Grimm 9/2812O22 Eaton Fayetteville,NC
disclosed In cgnfTdsflci and ft Ii only to APPROVED DATE J�NANE CCIJAPstan Creak WIMP
be used forth'purpose in which It la
supplied. DESIGNATION MCC-7
VERSION TYPE DRAWING TYPE
t.D.2.B Freedom+MCC Customer Appr.
NEOALT Number REVISION DWO SIZE G.O. ITEM Sh EET
.nRsu706x2104003 A - 3 of 4
.U1 [111632911B9 Description Class Starter Slze Jigsaw Unit
HPIFL9 Elea Features
We Dlaa. Trio/Cllo
1F L3 PL1A Panelboard 80 Pnlbd Bkr,BAB 1 Pole 20A bkr
225A 120/208V 3PH
4W 42 CKT 5A10398.DWF
1 M 30 Kva 3 ph,440-480
/120-208V High
Eltidency Xfmr,60A Prl., 5A10398.DWF
110A Sec.Bkr.
2A 6"Door
2D FVC Contactor Size F208 3 Tm.Brk. 1 150VA Individual CPT,Fused
3[TM Ckt Brk] 50KW 3P 1 N.O.Starter Aux Contacts,Size 1-4
NONE 90 1 N.C.Starter Aux Contacts,Size 1-4
1 Motor Load Blodc(100A)
1 Pilot Light-10250T-LED(On)
1 Pilot Light-10250T-LED(Off)
1 3 Pos.Sel.Sw,10250T(Hand-Off-
Autos
2H LS PL1A Panelboard 18 Pnlbd Bkr,BAB 1 Pole 20A bkr
SECTION 2 100A 120/208V 3PH
4W 18 CKT 5A10398.DWF
2Ai1 #4-350 Kcmll 4/Ph
Main Lugs(Screw)
NONE
3B 12"Door
3D 12"Door
3F 100KA,SPD Standard
+Surge Counter
Features Package,with NONE
Circuit Breaker -
3H HFD Bkr(100Atrip) HFD 1 Motor Load Block(100A)
3P
NONE 100
3M *4-350 KcmII 4/Ph
Sub Feed Lugs(Screw
tO (Screw) NONE
The Information on this document Is PREPARED BY DATE
created by Eaton Corporadon.It Is Daniel Griffin 512E/2022 Eaton Fayetteville, NC
Modem!In confidence and It le only to
be used for the purpose In which It Is APPROVED BY DATE JOB NAME CCUA Peters Creek WWTP
suppllsd. DESIGNATION MCC-7
VERSION TYPE I DRAWING TYPE
Freedom+MCC Cuetomar Appr.
NEO AALT Number REVISION ONO ME 0.0. ITEM SHEET
JV1ao70sX2K1-09e3 A 1 4 of 4
MCC General Information
MCC General Information Nameplate Color Black/White Letters
Wring Diagram Type Eaton Standard Overload Heater Packs Supplied
MCC Quantity Pilot Dev.Model 10250T
Standards UL845,NEMA,NEC Ind.Light Type 6v Xfmr
Special Codes UL PL Color(On) Red
Service Voltage(3 Phase) 480 PL Color(Off) Green
Frequency 60 PL Color(O.L.Trip) Blue
System 3PH3W PL Color(Mlsc) White
Witness Testing No
Structure Schedule
Enclosure Specifications There are 7 structure(s).
Total Structures 7 All structures have a 800 A vertical bus.
Type NEMA 12 Dust tight Total width of al sections Is 160"
Depth 21"Front Mt Only Height of al sections Is 91"
Height 90"
Horizontal Wreways 9"High,Top&Bottom Unit Modifications
Vertical Wlreways 4" #16awg,MTW Control Wlre
Channel Sills Yes BI-MetaNc Overload Relay(Standard)c/w Heater Packs
Bottom Plates Standard Terminal Block-Latching Pull-Apart,Std.
150 Watt Space Heaters No Wiremarkers at Each End
Space Heater Thermostat 1 Coll Surge Suppressor
Master Terminal Block Location None Beater Packs Suppled
IBC/CBC Seismic Qualified No
ABS Certified No
Bus System Specifications
Main Bus Amps 600
Main Bus Material Copper
Main Bus Bar Plating Tin
Insulated Horiz.Bus No
1000A/sq In.Cu Bus No
Vertical Bus Amps See Structure Schedule
Vertical Bus Material Tin Plated Copper
Vertical Bus Barrier Labyrinth,Isolated/
to Insulated with shutters
Bus Bracing 65,000
Ground Bus 300
Ground Bus Location Bottom
Ground Bus Lug Size 1350Kcmll
Ground Bus Lug Type Screw
Plug-In 300A Vert.Gnd.Bus No
Neutral None
Horizontal Bus Temperature Rise 65 deg C
Bottom Vert.Bus Baffler Yes
Vertical Ground Bus No
Incoming Line Termination
<Text columnspan="2">Devlce:#2-600
KcmII 2/Ph Main Lugs(Screw)&CTs</
Text>
Cable Entry Bottom
Splice Kit/Transition None
MCC Type Match Up
MCC Type Match Up GO# "None""
MCC Starter Specifications
Wring Class 28
Control Voltage 120
r Control Voltage Src Ind CPT
Nameplate Size 1'X 2.5"
The Information on this document le PREPARED BY DATEI
created by Eaton Corporation.It le Daniel Gr1Rln W25/2022 Eaton Fayetteville, NC
disclosed In confidence and It Is only to
be used for the purpose In which It Ise APPROVED BY DATE JOB NAME CCUA Peters Creek WWTP
supplied. I DESIGNATION MCC-3
VERSION TYPE DRAWING TYPE
1.0.2.e Frssdom+MCC CuetomerAppr.
NEO.ALT Number REVISION MO ERE G.D. ITEM SHEET
.Ivr3o7o5X2K14003 A I of B
Notes/Speclal Instructions
METER TO BE PXM2280
AR RELAY IN CLARIFIER TO BE LATCHING RELAY
PROVIDE EATON D65 3 PHASE VM IN METERING UNIT WITH OUTPUT CONTACTS RUN TO TB.
to
The Information on this document Is PREPARED BY DATE
created by Eaton Corporation.It is 8/2W2022 Eaton Fayetteville, NC
disclosed In confidence and k is only to
be used for the purpose in whkh it IS APPROVED BY DATE JOB NAME CCUA Peters Creek loWl TP
supplied. DESIONATioN MCC-3
VERSION TYPE DRAINING TYPE
1.0.2.8 Freedom+MCC CustomerAppr.
NEO.ALT Number REVISION DWG SIZE 0.0. ITEN SHEET
JV730706X$K1.900E A 2 of
Top View
I
5.�41 5.41 5.41 y J,
-'T.� t^IT.'3� 37.0 '� t^IT'f"�` t�T'`f'�
1F 2F 3F I 4F 5F 6F 7F
A
B DG1 Drive
FR6 •
C 205A CT .
D
E M, M R
F
G 2tT 2T 2gT FVNR S1 SPD
H M■rIE M■ MLO
J
K FVNR S2 FVNR S1 FVNR S1
, 1 .
to L , .,rui ni
M HFD3040 HFD3020
l<20.156_x 20.078* 40.078 'k-20.078*20.078*20.078> 20.078'.
1.25 1.25 1.25 1.25 1.25 1.25 1.25
-F -F -,F -F -F -F -F
j .
oA
co 1.25 1.25 1.25 1.25 1.25 1.25 1.25
g F 1 � 1 F- 1 F �, »- 1 ^ �. 4
v� 4 f x X I x mac` 3K YC Y
20.156 20.078 40.078 20.078 20.078 20.078 20.078
Floor View
The Infennatkn on this document Is PREPARED DY DATE
crrabed by Eaton Corporation.k N Dude/Griffin 9/28/2022 Eaton Fayetteville,NC
dlsckaad In eonfldanea and k N enly to •-
be used for the purpose In whkh k Is APPROVED BY DATE JOB NAME CCUA Peters Creek WWTP
supplied. DESIGNATION MCC$
~VERSION TYPE DRAWING TYPE
1.0.2.8 L Freedom+MCC Customer Appr.
NEG-ALT Number REVISION DWG SDE G.O. ITEM CHEET
JV78D7DSX2K1.0003 , A 3 of 9
la eta DantMa Qlala meter SIB [ Unit
I:IPLELA Psis Features
IOirtDiag. Idp/CIIR
1 B 12"Door
1 D 12"Door
1 F 12"Door
1H 12"Door
1K 12"Door
1 M 12"Door
2G RAS DG1 VFD,Constant HMCP 1 Blank Device Panel
torque, 23 FLA, 15/23 3P 1 DG1 Dv/Dt Output Filter-FR2
480V,HMCP NONE 30 1 3 Pos.Sel.Sw.,10250T(Hand-Off-
Auto)
1 Pilot Light-10250T-LED(Overload
Trip)
3 C-H Model D7,300V,4 Pole Socket
Relay
1 Motor Load Block(100A)
1 Pilot Light-10250T-LED(On,Run,
Fast,Forward)
1 Pilot Light-10250T-LED(Off,
Stopped)
1 Sr Pot 1000 Ohm
2J 12"Door
2M 18"Door
3M AERATOR DG1 VFD,Constant HMCP 1 Blank Device Panel
torque, 205 FLA, 150/205 3P 1 DG1 Dv/Dt Output Filter-FR6
480V,HMCP NONE 400 1 Speed Pot 1000 Ohm
1 3 Pos.Sel.Sw., 10260T(Hand-Off-
Auto)
6 C-H Model D7,300V,4 Pole Socket
Relay
1 Pilot Light-10250T-LED(Overload
Trip)
1 Pilot Light-10250T-LED(Misc)
1 C-H Model TRN Solid State On-
Delay Timer
to 1 1 Unit PB,10250T(Reset)
1 Pilot Light-10250T-LED(On,Run,
Fast,Forward)
1 Pilot Light-10250T-LED(Off,
i ed
4G WAS DG1 VFD,Constant HMCP 1 Blank Device Panel
torque, 23 FLA, 15123 3P 1 DG1 Dv/Dt Output Filter-FR2
480V,HMCP NONE 30 1 3 Pos.Sel.Sw.,10250T(Hand-Off-
Auto)
1 Pilot Ught-10250T-LED(Overload
Trip)
4 C-H Model D7,300V,4 Pole Socket
Relay
1 Motor Load Block(100A)
1 Pilot Ught-10250T-LED(On,Run,
Fast,Forward)
1 Pilot Light-10250T-LED(Off,
Stopped)
1 S.,<-,i Pot 1000 Ohm
4K POST AERATION FVNR Starter Size 2 F206 2 HMCP 1 150VA Individual CPT,Fused
BLOWER [HMCP] 20 3P 1 N.O.Starter Aux Contacts,Size 1-4
NONE 50 1 N.C.Starter Aux Contacts,Size 1-4
1 Pilot Light-10250T-LED(Misc)
2 C-H Model D7,300V,3 Pole Socket
Relay
1 3 Poe.Sal.Sw.,10250T(Hand-Off-
The Information on this document Is PREPARED BY DATE
created by Eaton Corporation.It Is Daniel Griffin ener2o.: Eaton Fayetteville, NC
disclosed In confidence and It I.only to —
be used for the purpose in which It Is APPRDVED m DATE JOB NAME CCUA Peters Creek WWTP
supplied. DESIGNATION MCC-3_
VERSION TYPE DRAINING TYPE
1.0.2.8 Freedom+MCC 1 CustomerAppr.
NEGALT Number REVISION DVYG SIZE Q0. ITB war
M5D706X2K1-0ooa A 4 of 13
Unit NameMale Datimirdign Clue Starter Size itisgby Unit
HPIELA Plalas Features
Ate Jag. TripfClD
Auto)
1 Motor Load Block(100A)
1 Pilot Light-10250T-LED(Run)
1 Pilot' ' ht-10250T-LED Stor r=-
4L 8"Door
4M 8'Door
5G RAS DG1 VFD,Constant HMCP 1 Blank Device Panel
torque, 23 FLA, 15/23 3P 1 DG1 Dv/Dt Output Filter-FR2
480V,HMCP NONE 30 1 3 Pos.Sel.Sw., 10250T(Hand-Off-
Auto)
1 Pilot Light-10250T-LED(Overload
Trip)
3 C-H Model D7,300V,4 Pole Socket
Relay
1 Motor Load Block(100A)
1 Pilot Light-10250T-LED(On,Run,
Fast,Forward)
1 Pilot Light-10250T-LED(Off,
Slopped)
1 Speed Pot 1000 Olen
5K PRIANOXIC FVNR Starter Size 1 F208 1 HMCP 1 150VA Individual CPT,Fused
MIXER [HMCP] 10 3P 1 N.O.Starter Aux Contacts,Size 1-4
NONE 30 1 N.C.Starter Aux Contacts,Size 1-4
1 Pilot Light-10250T-LED(Mtsc)
2 C-H Model D7,300V,3 Pole Socket
Relay
1 3 Pos.Sel.Sw., 10250T(Hand-Off-
Auto)
1 Motor Load Block(100A)
1 Pilot Light-10250T-LED(Run)
1 Pilot L ht-10250T-LED Sto j
6M HFD Bkr(40A trip) HFD 1 Motor Load Block(100A)
3P
NONE 40
to 8B 12"Door
8D 12"Door
8G SCUM PUMP FVNR Starter Size 1 F208 1 HMCP 1 160VA Individual CPT,Fused
[HMCP] 10 3P 1 N.O.Starter Aux Contacts,Size 1-4
NONE 30 1 N.C.Starter Aux Contacts,Size 1-4
2 Pilot Light-10250T-LED(Mc)
2 C-H Model D7,300V,3 Pole Socket
Relay
1 C-H Model TRN Solid State On-
Delay Timer
1 3 Pos.Sel.Sw.,10260T(Hand-Off-
Auto)
1 Motor Load Block(100A)
1 Pilot Light-10250T-LED(Run)
1 Pilot Light-10250T-LED!Stormed!
8K CLARIFIER FVNR Starter Size 1 F208 1 HMCP 1 150VA Individual CPT,Fused
[HMCP] 10 3P 1 N.O.Starter Aux Contacts,Size 1-4
NONE 30 1 N.C.Starter Aux Contacts,Size 1-4
1 2 Unit PB,10250T(Start/Stop)
1 C-H Model AR Machine Tool Relay,
800V,8 Pole
1 Motor Load Block(100A)
1 Pilot Light-10250T-LED(Run)
1 Pilot Lt_ht-10250T-LED Stoi
8M HFD Bkr(20A trip) HFD 1 Motor Load Block(100A)
3P
Thu Information on this document is PREPARED BY DATE
created by Eaton Corporation.It Is Daniel cretin 912812022 Eaton Fayetteville, NC
disclosed In confidence and It Is only to
be used for the purpose in which It Is APPROVED BY DATE Joe NAME CCUAPsters Creek WWTP
supplied. DESIGNATION MCC-3
VERSION TYPE DRAWING TYPE
1.02.8 Freedom+MCC Customer Appr.
NEG-ALTNumber REVISION DWG SIZE MO. ITEM SHEET
.Ar7307o6X2K1-o0oa A ___ 5 of 8
111311 flitMe12101 Descrinflon aggi starter Ste Skr/Sw
HP/FLA Pole& &MU =
Wire Dlag. I1112Clin
NONE 20
7B 12"Door
7E PXM2270
NONE
7G 300KA,SPD Standard
+Surge Counter
Features Package,with NONE
Circuit Breaker
7M #2-600 Kanli 2/Ph
Main Lugs(Screw)&
CTs NONE
to
The information on this document Is PREPARED BY DATE
created by Eaton Corporaflon.It is Daniel&Mtn 6126/2022 Eaton Fayetteville, NC
disclosed in confidence and It Is only to
be used for the purpose in which It Is APPROVED BY DATE JOB NAME CCUA Peters Creek W WTP
supplied. DEBIONATION MCC-9
VERSION TYPE DRAYNNGTYPE
1.0,2.6 Freedom+MCC CustomerAppr.
NEO,ALTNumb.r REVISION Dvra Sig O.O. n&1 SHEET
JMOT ex?K1-coca A 6 of 6
MCC General Information
MCC General Information Nameplate Color Black/White Letters
Wiring Diagram Type Eaton Standard Overload Heater Packs Supplied
MCC Quantity Pilot Dev.Model 10250T
Standards UL845,NEMA,NEC Ind.Light Type 8v Xfmr
Special Codes UL PL Color(On) Red
Service Voltage(3 Phase) 480 PL Color(OM Green
Frequency 80 PL Color(O.L.Trip) Blue
System 3PH3W PL Color(Mlsc) White
Witness Testing No
Structure Schedule
Enclosure Specifications There are 8 structure(s).
Total Structures 6 Al structures have a 800 A vertical bus.
Type NEMA 12 Dust tight Total width of all sections is 140"
Depth 21"Front Mt Ordy Height of all sections is 91'
Height 90"
Horizontal Wreways 9"High,Top&Bottom Unit Modifications
Vertical Wlreways 4" #16awg,MTW Control Wire
Channel Sills Yes BI-Metalic Overload Relay(Standard)ctw Heater Packs
Bottom Plates Standard Terminal Block-Latching Pull-Apart,Std.
150 Watt Space Heaters No Wiremarkers at Each End
Space Heater Thermostat 1 Coll Surge Suppressor
Master Terminal Block Location None Heater Packs Supplied
IBC/CBC Seismic Qualified No
ABS Certified No
Bus System Specifications
Main Bus Amps 600
Main Bus Material Copper
Main Bus Bar Plating Tin
insulated Hertz.Bus No
1000A/sq in.Cu Bus No
Vertical Bus Amps See Structure Schedule
Vertical Bus Material Tin Plated Copper
Vertical Bus Barrier Labyrinth,isolated/
to insulated with shutters
Bus Bracing 85,000
Ground Bus 300
Ground Bus Location Bottom
Ground Bus Lug Size 1-#8-350Kcmii
Ground Bus Lug Type Screw
Plug-In 300A Vert.Gnd.Bus No
Neutral None
Horizontal Bus Temperature Rise 85 deg C
Bottom Vert.Bus Barrier Yes
Vertical Ground Bus No
Incoming Line Termination
Text coiumnspan="2">Device:#2-800
Kcmil 2/Ph Main Lugs(Screw)&CTsd
Text>
Cable Entry Bottom
Splice Kit/Transition None
MCC Type Match Up
MCC Type Match Up GO# "None"
MCC Starter Specifications
Wring Class 2B
Control Voltage 120
Control Voltage Src Ind CPT
Nameplate Size 1"X 2.5"
The Information on this document Is PREPARED BY DATE
created by Eaton Corporation.It Is Daniel Griffin II/28/2022 Eaton Fayetteville, NC
diselosad t»conildanea and It Is only to
be used forts purpose In which It Is APPROVED BY DATE JOB RAAE CCUA Peters Creek WHIP
supplied. DESIGNATION MCC-4
VERSION TYPE DAAWNOTYPE
1.0.2.8 Freedom+MCC CustomerAppr.
NEG-ALTNumb.r REVISION DWG 812E G.O. ITEM eaST
JV730705x2KI.0003 A I of 5
Notes!Spec lal Instructions
METER TO BE PXM2280
AR RELAY IN CLARIFIER TO BE LATCHING RELAY
PROVIDE EATON D65 3 PHASE VM IN METERING UNIT WITH OUTPUT CONTACTS RUN TO TB.
to
The Information on this document Is PREPARED BY DATE
created by Eaton Corporation.It Is Daniel Griffin eneno22 Eaton Fayetteville, NC
disclosed In confidence end It is to
be used for the purpose In whrch It Is APPROVED BY DATE JOB NUE CCUA Peters Creek WWrP
supplied. DESIGNATION MCC-4
VERSION TYPE DRAIAANG TYPE
1.0.2.0 Freedom+MCC Customer Appr.
NEG,ALT Numb r REVISION DVAT SIZE G.O. ITEM SET
J ITTO7 6l2Kl.oos A 2 of 6
Top View
5.41 5.41 5y.41 5.41 5.41 5.41
t 14) < 14> < 1,. > < I7.> ( ,37.5 'ILTT3
1F 2F 3F 4F 5F 6F
A
B "n ■ DG1 Drive
FR6 C •
205A CT
D FVNR Si
,
E MTR 1M■
F
...
G SPD FVNR S1
H MLO mi. 2T 2T
J FVNR S11 �■
K HFD3050
to L . I MI
FVNR S2
M HFD3050 HFD3050
I<20.156*20.078*20.078>I<20.078* 40.078 >I<20.078
1.25 1.25 1.25 1.25 1.25 1.25
->4- -F -F -F -F ->F
to�—
I c m 1.25 1.25 1.25 1.25 1.25 1.25
� � -> E �� � y � E-
y -> E— y
20.156 20.078 20.078 20.078 40.078 20.078
Floor View
The information on We document I. PREPARED BY DATE
created by Eaton Corporation.It Is Dam,' Eaton Fayetteville,NC
disclosed In confidence and It Is only to - — —
be used for the purpose In which It Is APPROVED BY DATE JOB NAME CCUA Peters Creek WNTP
supplied. DESIGNATION MCC-4
4
VERSION TYPE DRAWING TYPE
1.D2.8 Freedom+MCC Customer Appr.
NEGALT Number REVISION DWG BIB GA. REM I SI{EET
JV730TO6X2K4.0003 1 A 1 3dd6
Unit Nemolila LtaargUlm Class starter S[za Bluffly Unit
HP/FLA Pyles Features
Wire Dlaa. Trip/Clip
1 B 12"Door
1 E PXM2270
NONE
1G 300KA,SPD Standard
+Surge Counter
Features Package,with NONE
Circuit Breaker
1M #2-600 Kcmll 2/Ph
Main Lugs(Screw)&
CTe NONE -
2A _ 6"Door
2D PRI ANOXIC FVNR Starter Slze 1 F206 1 HMCP 1 150VA Individual CPT,Fused
MIXER [HMCP] 10 3P 1 N.D.Starter Aux Contacts,Size 1-4
NONE 30 1 N.C.StarterAux Contacts,Size 1-4
1 Pilot Light-10250T-LED(Mist)
2 C-H Model D7,300V,3 Pole Socket
Relay
1 3 Pos.Sel.Sw.,10250T(Hand-Off-
Auto)
1 Motor Load Block(100A)
1 Pilot Light-10250T-LED(Run)
1 Pilot Li ht-10250T-LED Stor:
2G SCUM PUMP FVNR Starter Size 1 F208 1 HMCP 1 150VA Individual CPT,Fused
[HMCP] 10 3P 1 N.O.Starter Aux Contacts,Size 1-4
NONE 30 1 N.C.Starter Aux Contacts,Size 1-4
2 Pilot Light-10250T-LED(Mist)
2 C-H Model D7,300V,3 Pole Socket
Relay
1 C-H Model TRN Solid State On-
Delay Timer
1 3 Pos.Sel.Sw., 10250T(Hand-Off-
Auto)
1 Motor Load Block(100A)
1 Pilot Light-10250T-LED(Run)
tO 1 Pilot Light-10250T-LED Sto 7.
2K CLARIFIER FVNR Starter Size 1 F206 1 HMCP 1 150VA Individual CPT,Fused
[HMCP] 10 3P 1 N.O.StarterAux Contacts,Size 1-4
NONE 30 1 N.C.Starter Aux Contacts,Size 1-4
1 2 Unit PB,10250T(Start/Stop)
1 C-H Model AR Machine Tool Relay,
600V,6 Pole
1 Motor Load Block(100A)
1 Pilot Light-10250T-LED(Run)
1 Pilot LI ht-10250T-LED Stopped)
2M HFD Bkr(50A trip) HFD 1 Motor Load Block(100A)
3P
NONE 6Q
3A 6"Door
3H RAS DG1 VFD,Constant HMCP 1 Blank Device Panel
torque, 23 FLA, 15/23 3P 1 DG1 Dv/Dt Output Filter-FR2
480V,HMCP NONE 30 1 3 Pos.Sel.Sw., 10250T(Hand-Off-
Auto)
1 Pilot Light-10250T-LED(Overload
Trip)
3 C-H Model D7,300V,4 Pole Socket
Relay
1 Motor Load Block(100A)
1 Pilot Light-10250T-LED(On,Run,
Fast,Forward)
1 Pilot Light-10250T-LED(Off,
The Information on this document Is PREPARED BY DATE
crested by Eaton Corporation.It is DanielGriffin er2s/2022 Eaton Fayetteville,NC
disclosed In confidence end It is only to - —
be used for the purpose In which It le APPROVED BY DATE JOB NAME CCUA Peters Creek WIMTP
supplied. DC810NADON MCC-4
•
VERSION TYPE DRAWING TYPE
f.D 2.8 Freedom+MCC CustomerAppr.
NEG-ALTNumber REVISION Dw0SIZE 0.0. rDEM SHEET
JV730706X2K14003 A I 4 05
Unit Nameplate Description Class starter Size Bkr/S I Unit
HPIELA E211211 Features
wee Dlag. Trip/Clip
Stopped)
1 Si-eed Pot 1000 Ohm
3K HFD Bkr(50Atrip) HFD 1 Motor Load Block(100A)
3P
NONE 50
3M HFD Bkr(60A trip) HFD 1 Motor Load Block(100A)
3P
NONE _ 50
4A 8"Door
4H WAS DG1 VFD,Constant HMCP 1 Blank Device Panel
torque, 23 FLA, 15r23 3P 1 DG1 Dv/Dt Output Filter-FR2
480V,HMCP NONE 30 1 3 Pos.Sel.Sw., 10250T(Hand-Off-
Auto)
1 Pilot Light-10250T-LED(Overload
Trip)
4 C-H Model D7,300V,4 Pole Socket
Relay
1 Motor Load Block(100A)
1 Rot Light-10250T-LED(On,Run,
Fast,Forward)
1 Pilot Light-10250T-LED(Off,
Stopped)
1 Soeea Pot 1000 Ohm
4L POST AERATION FVNR Starter Size 2 F206 2 HMCP 1 150VA Individual CPT,Fused
BLOWER [HMCP] 20 3P 1 N.O.StarterAux Contacts,Size 1-4
NONE 60 1 N.C.Starter Aux Contacts,Size 1-4
1 Pilot Light-10260T-LED(Mc)
2 C-H Model D7,300V,3 Pole Socket
Relay
1 3 Pos.Sel.Sw., 10260T(Hand-Off-
Auto)
1 Motor Load Block(100A)
1 Pilot Light-10250T-LED(Run)
1 Pilot L i ht-10250T-LED St J:
to 4M B"Door 5M AERATOR DG1 VFD,Constant HMCP 1 Blank Device Panel
torque, 205 FLA, 150/206 3P 1 DG1 Dv/Dt Output Filter-FRO
480V,HMCP NONE 400 1 Speed Pot 1000 Ohm
1 3 Pos.Sel.Sw., 10260T(Hand-Off-
Auto)
B C-H Model D7,300V,4 Pole Socket
Relay
1 Pilot Light-10250T-LED(Overload
Trip)
1 Pilot Light-10250T-LED(Mlac)
1 C-H Model TRN Solid State On-
Delay Timer
1 1 Unit PB, 10260T(Reset)
1 Pilot Light-10250T-LED(On,Run,
Fast,Forward)
1 Pilot Light-10250T-LED(Off,
St
BB 12"Door
SD 12"Door
SF 12"Door
8H 12"Door
BK 12"Door
BM 12"Door
The Information on this document Is PREPARED BY DATE
crested by Eaton Corporation.It Is -lei Griffin w.argon Eaton Fayetteville, NC
disclosed in confidence and It Is only to
be used for the purpose in which It Is APPROVED BY DATE JOB NAME CCUAPetsn CreekWWTP
supplied. DESIONATTON MCC-4 _
VERSION TYPE DRAWING TYPE
1.0.2.8 Fresdom+MCC Customer Appr.
NEG-ALT Number REVISION DWG WIRE am. ITEM SHEET
�evramoexzln 000a A I 5 of 5
MCC General Information
MCC General Information Pilot Dev.Model 10250T
Wring Diagram Type Eaton Standard Ind.Light Type 8v Xfmr
MCC Quantity PL Color(On) Red
Standards UL845,NEMA,NEC PL Color(Off) Green
Special Codes UL PL Color(O.L.Trip) Blue
Service Voltage(3 Phase) 480
Frequency 80 Structure Schedule
System 3PH3W There are 8 stru ture(s).
Witness Testing No All structures have a 600 A vertical bus.
Total width of all sections Is 160"
Enclosure Specifications Height of all sections Is 91"
Total Structures 8
Type NEMA 1 Gasketed Unit Modifications
Depth 21"Front Mt Only #18awg,MTW Control Wre
Height 90" BI-Metalle Overload Relay(Standard)c/w Heater Packs
Horizontal Wlreways 9"High,Top&Bottom Terminal Block-Latching Pull-Apart,Std.
Vertical Wireways 4" Wiremarkers at Each End
Channel Sills Yes Coil Surge Suppressor
Bottom Plates None Heater Pads Supplied
150 Watt Space Heaters No
Space Heater Thermostat 1
Master Terminal Block Location None
IBC/CBC Seismic Qualified No
ABS Certified No
' Bus System Specifications
Main Bus Amps 800
Main Bus Material Copper
Main Bus Bar Plating Tin
Insulated Horiz.Bus No
1000A1sq In.Cu Bus No
Vertical Bus Amps See Structure Schedule
Vertical Bus Material Tin Plated Copper
Vertical Bus Barrier Labyrinth,Isolated/
to Insulated with shutters
Bus Bracing 85,000
Ground Bus 300
Ground Bus Location Bottom
Ground Bus Lug Size 1-#8-350Kcmil
Ground Bus Lug Type Screw
Plug-in 300A Vert.Gnd.Bus No
Neutral None
Horizontal Bus Temperature Rise 85 deg C
Bottom Vert.Bus Barrier Yea
Vertical Ground Bus No
Incoming Line Termination
Device:NGH-C Main Bkr(800Atip),Lugs:4-#4/0-500Kcmll
Cable Entry Bottom
Splice Kit/Transition None
MCC Type Match Up
MCC Type Match Up GO# "None"
MCC Starter Specifications
Wiring Class 2B
Control Voltage 120
Control Voltage Src Ind CPT
Nameplate Size 1"X 2.5"
Nameplate Color Black/White Letters
Overload Heater Packs Supplied
The Information on this document Is PREPARED BY DATE
crested by Eaton Corporation.ft Is I panel Griffin 9/2el2022 Eaton Fayetteville,NC
disclosed In confidence and It le only to -
be used for the purpose In which ft Is I A—PPRD ED BY DATE JOS NAME CCUA Peters CreakWiNTP
supplied. DESIGNATION MCC-5
VERSION TYPE DRAIMNO TYPE
1.02.8 Freedom+MCC Customer Appr.
NEG-ALT Nurnbif REVISION DWG Sri 0.0. ITEM SFEET
JY730705X2K1.0003 A 1 of 5
Notes/Special Instructions
METER TO BE PXM2280
PROVIDE EATON D65 3 PHASE VM IN METERING UNIT WITH OUTPUT CONTACTS RUN TO TB.
COORDINATE KIRK KEY WITH MCC-6
to
The Informatlon on this document Is I PREPARED BY DATE i
crested by Eaton Corporation.R Is Dmy1 t3rlM tu2e12o22 Eaton Fayetteville,NC
disclosed In confidence and It is only to
be used for the purpose In which It Is APPROVED BY DATE JOB NAME CCUA Peters Creek 4WVTP
supplied. DESIGNATION MCC-6
VERSION TYPE DRAINING TYPE
1.0.2.8 Freedom+MCC CustomerAppr.
NEG•ALT Wolin( REVISION DWG WE O.O. ITEM SHEET
JV7a0706 1.00Da A _ _ 2 of 5
Top View
5.4,1 5.�4,1 5.�4,�,1 5.4,1 5.4,1 5.4,1 5.y41 5..41
1 r.�} ,F 71 `—r' 17. E -1T.5; <i 7..9'> �c< ; --Tr j
1F 2F 3F 4F 5F 6F 7F 8F
B DG1 Drive DG1 Drive DG1 Drive DG1 Drive DG1 Drip€
HJD3250 FR5 FR5 FR5 FR5 FR4
C
1 140A CT 140A CT 140A CT 140A CT 72A CT MTR
D
...
E SPD
F
III
G FVN•
H 1
J HFD3050
Lm
to L HFD30501
M VGH-C380 1
<20.156>I<20.078*20.078*20.078*20.078*20.078>IC 20.078*20.078
1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25
-F -F -,F -F -F -F -F -F
-1 — 1 I I ` I
N Co 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25
,t_ L 4, , 4, ____i_L __i_n, 4, 4,
20.156 20.078 20.078 20.078 20.078 20.078 20.078 20.078
Floor View
The Information on tins document Is PREPARED BY DATE
crested by Eaton Corporation.It a Daniel Griffin w er on Eaton Fayetteville,NC
disclosed in confidence end It Is only to —
be used for the purpose In which It Is APPROVED BY DATE JOB NAVE CCUA Peters Creek WWTP
supplied. DESIGNATION MCC-5
VERSION TYPE DRAWING TYPE
1.0.2.8 Freedom+MCC Customer Appr.
NEO-ALTNumber REVI61ON MO BM O.O. ITEM IIEET
11/730705X2K1-0008 I A 3of3
Unit Nameplate 12asszlollEm gin Starter SIze Bkr/Sw 1++0[t
HP/FLA EStIOFeatures
wag. Trip/Cup
1 C HJD Bkr(250A trip) HJD 1 Fdr Bkr Key Interlock
3P
NONE 260
1E 12"Door
1 G 12"Door
1J 12"Door
1M 18"Door
2M HIGH SERVICE DG1 VFD,Constant HMCP 1 Blank Device Panel
PUMP torque, 140 FLA, 100/140 3P 1 DG1 Dv/Dt Output Filter-FR5
480V,HMCP NONE 150 1 3 Pos.Sel.Sw.,10250T(Hand-Off-
Auto)
1 Pilot Light-10250T-LED(Overload
Trip)
3 C-H Model D7,300V,4 Pole Socket
Relay
1 Motor Load Block(100A)
1 Pilot Light-10260T-LED(On,Run,
Fast,Forward)
1 Pilot Light-10250T-LED(Off,
Stopped)
1 Speed Pot 1000 Ohm
3M HIGH SERVICE DG1 VFD,Constant HMCP 1 Blank Device Panel
PUMP torque, 140 FLA, 100/140 3P 1 DG1 DvlDt Output Filter-FR5
480V,HMCP NONE 150 1 3 Pos.Sel.Sw.,10250T(Hand-Off-
Auto)
1 Pilot Light-10250T-LED(Overload
Trip)
3 C-H Model D7,300V,4 Pole Socket
Relay
1 Motor Load Block(100A)
1 Pilot Light-10250T-LED(On,Run,
Fast,Forward)
1 Pilot Light-10250T-LED(Off,
gypped)
tO 1 3, • i Pot 1000 Ohm
4M TRANSFER PUMP DG1 VFD,Constant HMCP 1 Blank Device Panel
torque, 140 FLA, 100/140 3P 1 DG1 Dv/Dt Output Filter-FR6
480V,HMCP NONE 150 1 3 Pos.Sel.Sw,10250T(Hand-Oft-
Auto)
1 Pilot Light-10250T-LED(Overload
Trip)
3 C-H Model D7,300V,4 Pole Socket
Relay
1 Motor Load Block(100A)
1 Pilot Light-10250T-LED(On,Run,
Fast,Forward)
1 Pilot Light-10250T-LED(Off,
Stopped)
1 S eed Pot 1000 Ohm
5M EFFLUENT DG1 VFD,Constant HMCP 1 Blank Device Panel
torque, 140 FLA, 100/140 3P 1 DG1 Dv/Dt Output Filter-FR5
480V,HMCP NONE 150 1 3 Pos.Sel.Sw.,10250T(Hand-Off-
Auto)
1 Pilot Light-10250T-LED(Overload
Trip)
3 C-H Model D7,300V,4 Pole Socket
Relay
1 Motor Load Block(100A)
1 Pilot Light-10250T-LED(On,Run,
Fast,Forward)
The Information an Ns document Is PREPARED BY DATE
created by Eaton Corporation.It Is Daniel Gr,ffin a/28n022 Eaton Fayetteville,NC
disclosed In confidence end It Is only to ,—
be used for the purpose In which It Is APPROVED BY DATE JOB NAME CCUA Peters Creek WNTP
supplied. DESIGNATION MCC-5
VERSION TYPE DRAWING TYPE
1.02.E Freedom+MCC CustomerAppr.
NEG-ALTNumbsr REVISION DVASIT 0.0. ITEM SHEET
.M307oIX2X1-0003 A 4 or 5
S101t Namt In Dame ieIlan Class Staff Sin Elir/Sw Unit
HPIELA Blaa Eftat1220.1
Zia Oka. Trip/Clip
1 Pilot Light-10250T-LED(Oft,
Stopped)
1 S. Pot 1000 Ohm
8M EFFLUENT DG1 VFD,Constant HMCP 1 Blank Device Panel
torque, 72 FLA, 60/72 3P 1 DG1 Dv/Dt Output Fitter-FR4
480V,HMCP NONE 100 1 3 Pos.Sel,Sw.,10250T(Hand-Off-
Auto)
1 Pilot Light-10250T-LED(Overload
Trip)
3 C-H Model D7,300V,4 Pole Socket
Relay
1 Motor Load Block(100A)
1 Pilot Light-10250T-LED(On,Run,
Fast,Forward)
1 Pilot Light-10250T-LED(Off,
Stopped)
1 Speed Pot 1000 Ohm
7C PXM2270
NONE
7E 300KA,SPD Standard
+Surge Counter
Features Package,with NONE
Circuit Breaker
7G REUSE FVNR Starter Slze 2 F206 2 HMCP 1 150VA Individual CPT,Fused
[HMCP] 26 3P 1 N.O.Starter Aux Contacts,Size 1-4
NONE 70 1 N.C.Starter Aux Contacts,Size 1-4
1 3 Pos.Sel.Sw., 10260T(Hand-Off-
Auto)
i C-H Model D7,300V,2 Pole Socket
Relay
1 Pilot Light-10250T-LED(Run)
1 Pilot Light-10250T-LED(Stopped)
1 Pilot Light-10250T•LED(Overload
Trip)
to 1 Motor Load Block 1,,I
7J HFD Bkr(50A trip) HFD 1 Motor Load Block(100A)
3P
NONE 50
7L HFD Bkr(50A trip) HFD 1 Motor Load Block(100A)
3P
NONE 50
7M 6"Door
8M NGH-C Maln Bkr NGH-C 1 RMS 310+LSI Trip
(800A trip),Lugs: 3P 1 Main Bkr Auxiliary Interlock 1NO-
1NC
4#4/0-500Kcmil NONE 800 1 Alarm Contact Circuit Breaker Sw.
The inlormetlon on this document Is I PREPARED BY DATE
crated by Eaton Corporation.It is Daniel Griffin9/25/2022 Eaton Fayetteville, NC
disclosed In confidence and It Is only to
be used for the purpose In which It la APPROVED BY DATE JOB NAME CCUA Peters Creek WARP
supplied. DESIGNATION MCC-5
VERSION TYPE DRAWING TYPE
1.0.2.5 Freedom+MCC CustomerAppr.
NEG-ALTNumber REVISION DWG SIZE 0.0. ITEM SHEET
JV78oToax2K1.0o921 A 1 5 of 6
MCC General Information
MCC General Information Plot Dev.Model 10250T
Wring Diagram Type Eaton Standard Ind.Light Type 6v Xfmr
MCC Quantity PL Color(On) Red
Standards UL845,NEMA,NEC PL Color(Off) Green
Special Codes UL PL Color(O.L.TNp) Blue
Service Voltage(3 Phase) 480
Frequency 80 Structure Schedule
System 3PH3W There are 7 structure(s).
Wftneas Tbsting No All structures have a 800 A vertical bus.
Total width of all sections la 140"
Enclosure Specifications Height of all sections Is 91"
Total Structures 7
Type NEMA 1 Gasketed Unit Modifications
Depth 21"Front Mt Only t16awg,MTW Control Wire
Height 90" BI-Metalc Overload Relay(Standard)c/w Heater Packs
Horizontal Wreways 9"High,Top&Bottom Terminal Block-Latching Pull-Apart,Std.
Vertical Wreways 4" Wlremarkera at Each End
Channel Sills Yes Coll Surge Suppressor
Bottom Plates None Heater Packs Suppled
150 Watt Space Heaters No
Space Heater Thermostat 1
Master Terminal Block Location None
IBC/CBC Seismic Qualified No
ABS Certified No
Bus System Specifications
Main Bus Amps 800
Main Bus Material Copper
Main Bus Bar Plating Tin
Insulated Hartz.Bus No
1000A/sq In.Cu Bus No
Vertical Bus Amps See Structure Schedule
Vertical Bus Material Tin Plated Copper
Vertical Bus Barrier Labyrinth,Isolated/
to Insulated with shutters
Bus Bracing 65,000
Ground Bus 300
Ground Bus Location Bottom
Ground Bus Lug Size 148-350KCml
Ground Bus Lug Type Screw
Plug-in 300A Vert Gnd.Bus No
Neutral None
Horizontal Bus Temperature Rise 85 deg C
Bottom Vert,Bus Barrier Yes
Vertical Ground Bus No
Incoming Line Termination
Device:NGH-C Main Bkr(800A trip),Lugs:4-#4/0-500Kcmil
Cable Entry Bottom
Splice fat/Transition None
MCC Type Match Up
MCC Type Match Up GO# "None"
MCC Starter Specifications
Wring Class 2B
Control Voltage 120
Control Voltage Src Ind CPT
Nameplate Sze 1"X 2.5"
Nameplate Color Black J White Letters
Overload Heater Packs Supplied
The Information on this document Is PREPARED BY DATE
created by Eaton Corporation.it Is Daniel Griffin W2612022 Eaton Fayetteville, NC
disclosed In confidence end It Is only to be used for the purpose In which k is APPROVED BY DATE JOB NAME CCUA Peters Creek WWTP
supplied. DaIONATION MCC-0
MINION TYPE IDRANMNeTYPE
1.0.2.11 Freedom+MCC Customer Apar.
NEO-ALT Number REVISION DWI SIZE G O. ITEM SHEET
.Nr30705X2K1-0003 I A 1 of 5
Notes/Special Instructions
METER TO BE PXM228O
PROVIDE EATON D035 3 PHASE VM IN METERING UNIT WITH OUTPUT CONTACTS RUN TO TB.
COORDINATE KIRK KEY WITH MCC-5
I
to
'
The information on this document is PREPARED ET DATE
crested by Eaton Corporation.It a Daniel Griffin 812612022 Eaton Fayetteville, NC
disclosed In confidence and It Is only to APPROVED BY DATE JOB NAME gp Croak VVIAITP
be used forme purpose In which itis
supplied. DESIGNATION MCC!
VERSION TYPE 'DRAWING TYPE
1.02.6 Freedom+MCC Customer Appr•
NEG.ALT Numbs, REVISION DWO SIZE G.O. (ITEM SHEET
JVTSOT66X2K1.6665 l 1 2 of
Top View
41
--.�.T.* --mg— 17 - --mg—
1F 2F 3F 4F 5F 6F 7F
A
1111
B T DG1 Drive DG1 Drive DG1 Drive DG1 Driva
C MTR FR4 FR5 FR5 FR5 1HJD3250
72A CT 140A CT 140A CT 140A CT !
D ... I
E IR
SPD HFD3100j
F
G FVNR S2
H
J 1 HFD3050
K 31
to L HFD3050
M ',IGH-C380
ilia
<20.158*20.078>I<20.078*20.078*20.078*20.078>I<20.078)1
1.25 1.25 1.25 1.25 1.25 1.25 1.25
-F -E -F -F -+F --1F -F
` - --_ s
0 A
n1 m 1.25 1.25 1.25 1 •25 1.25 1.25 1.25
= -3 E- 1 F- 1 E- 11 —3 E- 11 —3 - 1 -) <. 11r
I'E- x x i E x ' x I 11 x >
20.156 20.078 20.078 20.078 20.078 20.078 20.078
Floor View
lThe Information on this document is PREPARED BY DATE
created by Eaton corporation,It Is Daniel Griffin e/28f2022 Eaton Fayetteville, NC
disclosed In confidence end It Is only to —
be used for the purpose In which It Is APPROVED BY DATE JOB NAME CCUA Peters Creek WWTP
Supplied. DESIGNATION MCC-e
VERSION TYPE DRAWING TYPE
1.02.8 Freedom+MCC CustomerAppr.
NEO-ALTNumber REVISION DINOau:E 0.0. ITEM SHEET
.nr7eo7oex2x1-0003 i A 3 of 5
Unit Nameplate Descilolltm Qua Starter Slag WM.& i[njt
HPJ LA P9lea Failures
Ala. Il llp
I M NGH-C Maln Bkr NGH-C 1 Main Bkr Auxiliary Interlock 1 NO-
1 NC
(800A trip),Lugs: 3P 1 Alarm Contact Circuit Breaker Sw.
4-#4/0-500K0m11 NONE 800 1 RMS 310+LSI Trt
2C PXM2270
NONE
2E 300KA,SPD Standard
+Surge Counter
Features Package,with NONE
Circuit Breaker
2G REUSE FVNR Starter Size 2 F208 2 HMCP 1 150VA Individual CPT,Fused
[HMCP] 25 3P 1 N.O.Starter Aux Contacts,Size 1-4
NONE 70 1 N.C.Starter Aux Contacts,Size 1-4
1 3 Pos.Sal.Sw.,10250T(Hand-Off-
Auto)
1 C-H Model D7,300V,2 Pole Socket
Relay
1 Pilot Light-10250T-LED(Run)
1 Pilot Light-10250T-LED(Stopped)
1 Pilot Light-10250T-LED(Overload
Trip)
1 Motor Load Block(100A)
2J HFD Bkr(50A trip) HFD 1 Motor Load Block(100A)
3P
NONE 50
2L HFD Bkr(50A trip) HFD 1 Motor Load Block(100A)
3P
NONE 50
2M 8"Door
3M EFFLUENT DG1 VFD,Constant HMCP 1 Blank Device Panel
torque, 72 FLA, 50/72 3P 1 DG1 Dv/Dt Output Filter-FR4
480V,HMCP NONE 100 1 3 Pos.Sel.Sw,10250T(Hand-Off-
Auto)
1 Rot Light-10250T-LED(Overload
Trip)
3 C-H Model D7,300V,4 Pole Socket
Relay
1 Motor Load Block(100A)
1 Pilot Light-10250T-LED(On,Run,
Fast,Forward)
1 Pilot Light-10250T-LED(Off,
Stopped)
1 Sp''d Pot 1000 Ohm
4M EFFLUENT DGI VFD,Constant HMCP 1 Blank Device Panel
torque, 140 FLA, 100/140 3P 1 DG1 DvIDt Output Filter-FR5
480V,HMCP NONE 150 1 3 Pos.Sel.Sw.,10250T(Hand-Off-
Auto)
1 Pilot Light-10250T-LED(Overload
Trip)
3 C-H Model D7,300V,4 Pole Socket
Relay
1 Motor Load Block(100A)
1 Pilot Light-10250T-LED(On,Run,
Fast,Forward)
1 Pilot Light-10250T-LED(Off,
Stopped)
1 Sp-ed Pot 1000 Ohm
5M TRANSFER PUMP DG1 VFD,Constant HMCP 1 Blank Device Panel
torque, 140 FLA, 100/140 3P 1 DG1 Dv/Dt Output Filter-FR5
480V, HMCP NONE 150 1 3 Pos.Sel.Sw., 10250T(Hand-Off-
The Information on thIs document I. PREPARED BY DATE
created by Eaton Corporation.It Is Dank)Griffin4/2ea022 Eaton Fayetteville, NC
disclosed In confidence and It la only to
be toad for Ma purpose In which It Is APPROVED BY DATE JOB NAME CCUAPolus Creek twrrP
supplied. DESIGNATION MCC4
VERSION TYPE DRAIMNGTVPa
1.0,2.E Freedom+MCC CustomerAppr.
NEWLLT Number REVISION DM SIZE O.O. rTE]M MEET
JV7307oSx2K1.0003 1 A 4 of 5
slot Na late DAIDBMI00 Cling Starter Size Bkrlsw Unit
HEM Pska Features
V i re_Diag. Trio/Cllo
Auto)
1 Pilot Light-10260T-LED(Overload
Trip)
3 C-H Model D7,300V,4 Pole Socket
Relay
1 Motor Load Block(100A)
1 Pilot Light-10250T-LED(On,Run,
Fast,Forward)
1 Pilot Ught-10250T-LED(Off,
Stopped)
1 S:.eec Pot 1000 Ohm
8M HIGH SERVICE DG1 VFD,Constant HMCP 1 Blank Device Panel
PUMP torque, 140 FLA, 100/140 3P 1 DG1 Dv/Dt Output Filter-FRS
480V,HMCP NONE 150 1 3 Pos.Bel.Sw,10250T(Hand-Off-
Auto)
1 Pilot Light-10250T-LED(Overload
Trip)
3 C-H Model D7,300V,4 Pole Socket
Relay
1 Motor Load Block(100A)
1 Pilot Light-10250T-LED(On,Run,
Fast,Forward)
1 Pilot Light-10250T-LED(Off,
Stopped)
1 SE:eed Pot 1000 Ohm
7C HJD Bkr(250Atrip) HJD 1 Fdr Bkr Key Interlock
3P
NONE 260
7E HFD Bkr(100Atrip) HFD 1 Motor Load Block(100A)
3P
NONE 100
7G 12"Door
7J 12"Door
7M 18"Door
to
The Informstlon on this document Is PREPARED BY DATE
created by Eaton Corporation.It le Daniel artrtin 11128/2022 Eaton Fayetteville,NC
disclosed In confidence end It is only to - - - ,
be used for the purpose In which it is APPROVED BY DATA JOB NAME CCUA Peters Creek IN rP
supplied. DESIGNATION MCC-0
VERSION TYPE DRAINING TYPE
1.0 2.a Freedom+MCC CustomerAppr.
NEO-ALTNumber REVISION DWESIZE O.O. ITEM SHEET
JV736706X2K1-0003 A 5 of 5